Plan Review Notes
Plan Review Notes For Permit 16080405
Permit Number 16080405
Review Stop E
Sequence Number 1
Notes
Date Text
2016-08-11 16:48:56ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 PROJECT NAME: 530 32ND ST.
 JOB ADDRESS: 530 32ND ST.
 DESCRIPTION: INTERIOR RENOVATION, RELOCATE KITCHEN, NEW
 MASTER BEDROOM EXISTING BATH.
 MASTER PERMIT: 16080405
 REVISION:
  
 BELOW ARE COMMENTS RELATED TO THE FAILED ELECTRICAL
 REVIEW: MOST OF WHICH MAY BE ADDRESSED WITH A BLOCK
 NOTE.
  
 1. FBC-E C402.4.8: RECESSED LIGHTING INSTALLED IN THE
 BUILDING THERMAL ENVELOPE SHALL BE IC RATED AND BE
 SEALED TO LIMIT AIR LEAKAGE BETWEEN CONDITIONED &
 UNCONDITIONED SPACES.
 2. FBC-R4001.15/NEC 404.2(C): WHERE SWITCHES
 CONTROLLING LIGHTING LOADS SUPPLIED BY A GROUNDED
 BRANCH CIRCUIT, THE GROUNDED BRANCH CIRCUIT CONDUCTOR
 FOR THE CONTROLLED LIGHTING CIRCUIT SHALL BE PROVIDED
 AT THE SWITCH.
 3. FBC-R404.1: A MINIMUM OF 75% OF THE LAMPS IN
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE
 HIGH-EFFICACY LAMPS OR A MINIMUM OF 75% OF THE
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN
 ONLY HIGH EFFICIENCY LAMPS
 4. FBC-RE3902.12/NEC 210.12(B): ALL NEW OUTLETS TO BE
 AFCI PROTECTED.
 5. FBC-R4002.14 NEC 406.12: IN ALL AREAS SPECIFIED IN
 210.52, ALL 125-VOLT, 15 AND 20 AMPERE RECEPTACLES
 SHALL BE LISTED TAMPER RESISTANT RECEPTACLES.
 6. FBC-RE4002.9/NEC 406.9(B): 15 AND 20 AMPERE, 125 AND
 250 VOLT RECEPTACLES INSTALLED IN A WET LOCATION SHALL
 HAVE AN ENCLOSURE THAT IS WEATHERPROOF WHETHER OR NOT
 THE ATTACHMENT PLUG CAP IS INSERTED. ALL 15 AND 20
 AMPERE, 125 AND 250 VOLT NONLOCKING RECEPTACLES SHALL
 BE LISTED WEATHER-RESISTANT TYPE ?WR?.
 7. FBC-R 314: YOU SHALL COME INTO COMPLIANCE WITH SMOKE
 DETECTOR REQUIREMENTS AS FOR NEW HOMES.
 8. FBC-R 315: YOU SHALL INSTALL CARBON MONOXIDE
 DETECTORS AS PER CODE.
 9. ON THE FLOOR PLAN NOTE THE LOCATION OF ALL SERVICE
 EQUIPMENT AS WELL AS ALL ELECTRICAL PANELS.
 10. NEC 215.5: PROVIDE A SITE SPECIFIC RISER DIAGRAM
 SHOWING THE LOCATION AND POSITION IN THE SERVICE OF THE
 TRANSFER SWITCH WITH RELATION TO ALL OTHER PANELS.
 INCLUDE ON THE RISER DIAGRAM CONDUCTOR SIZING.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  