| 2016-09-14 10:31:48 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) MAIN HOUSE SHALL COMPLY WITH FBC-R314.3.1 |
| | ALTERATIONS, REPAIRS AND ADDITIONS. |
| | WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE |
| | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| | LOCATED AS REQUIRED FOR NEW DWELLINGS. |
| | |
| | 2) MAIN HOUSE AND GUEST HOUSE SHALL COMPLY WITH |
| | FBC-R315.1 CARBON MONOXIDE PROTECTION. |
| | EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING |
| | BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS |
| | ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR |
| | APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER |
| | FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE |
| | AS A BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL |
| | CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH |
| | ROOM USED FOR SLEEPING PURPOSES. |
| | |
| | 3) THE HEADING UNDER GENERAL NOTES ON DRAWING SHEET 1, |
| | SPECIFIES AN ADDITION. CLEARLY INDICATE THE ADDED SPACE |
| | ON THE PLANS AND PROVIDE AREA TABULATIONS. FBC 107.2.1 |
| | |
| | 4) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 |
| | THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT |
| | APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION |
| | INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR THE NEW |
| | FRENCH DOORS. THE PLANS INDICATE THAT THE DOOR |
| | INSTALLATION IS TO BE UNDER A SEPARATE PERMIT, HOWEVER, |
| | THE OTHER PERMIT IS ONLY TO REPLACE THE WINDOWS IN THE |
| | GUEST HOUSE. |
| | |
| | 5) FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS AND |
| | COMPONENT AND CLADDING DESIGN PRESSURES PURSUANT TO |
| | FBC-R301.2. |
| | |
| | 6) YOU ARE REQUIRED TO PROVIDE A BOND BREAK BETWEEN THE |
| | EXTERIOR STUCCO AND THE WATER BARRIER PER FBC-R703.6.3 |
| | WATER-RESISTIVE BARRIERS. WATER-RESISTIVE BARRIERS |
| | SHALL BE INSTALLED AS REQUIRED IN SECTION R703.2 AND, |
| | WHERE APPLIED OVER WOOD-BASED SHEATHING, SHALL INCLUDE |
| | A WATER-RESISTIVE VAPOR-PERMEABLE BARRIER WITH A |
| | PERFORMANCE AT LEAST EQUIVALENT TO TWO LAYERS OF GRADE |
| | D PAPER. THE INDIVIDUAL LAYERS SHALL BE INSTALLED |
| | INDEPENDENTLY SUCH THAT EACH LAYER PROVIDES A SEPARATE |
| | CONTINUOUS PLANE AND ANY FLASHING (INSTALLED IN |
| | ACCORDANCE WITH SECTION R703.8) INTENDED TO DRAIN TO |
| | THE WATER-RESISTIVE BARRIER IS DIRECTED BETWEEN THE |
| | LAYERS. |
| | |
| | |