2016-08-11 11:18:44INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. ELECTRICAL SUB PERMIT REQUIRED.
 2. PLEASE ADD A GENERAL NOTE TO SHEET TO INDICATE THE
 REQUIREMENTS OF NEC 300.5D3 AND TABLE 300.5 FOR MINIMUM
 COVER REQUIREMENTS FOR CONDUITS. A NOTE WILL SUFFICE
 3. RISER DIAGRAM AND PANEL SCHEDULE- PLEASE PROVIDE
 AVAILABLE FAULT CURRENT AVAILABLE AT THE FPL SERVICE.
 ATTACH TO DOCUMENTS LETTER FROM FLORIDA POWER & LIGHT
 INDICATING AIC. SHOW AIC CALCULATION BASED ON
 INFORMATION PROVIDED BY UTILITY FOR APPROVAL. NEC
 110.24 FBC 107
 4. ONE-LINE DIAGRAM TO REFLECT CONDUIT, ELECTRODE
 CONDUCTOR, RATINGS AMPS, AND SERVICE AND FEEDERS
 CONDUCTOR SIZES THROUGHOUT, FUSE RATINGS ETC. SHOW A
 COMPLETE ONE-LINE. FBC 107.3.5 MINIMUM PLAN REVIEW
 CRITERIA
 5. PROVIDE A SUPPLEMENTAL GROUND ROD (2) 6FT APART AT
 SERVICE PER NEC 250.50 PART 3
 6. LABEL SERVICE EQUIPMENT TO BE RATED FOR SERVICE
 ENTRANCE AND IN COMPLIANCE WITH NEC 230.79 FOR MINIMUM
 SERVICE CAPACITY.
 7. SHOW LOADS CALCULATIONS PER NEC 220
 8. PROVIDE A GFCI/WP RECEPTACLE AT THE SERVICE FOR
 TEMPORARY POWER.
 9. PROVIDE AN INTERSYSTEM BONDING TERMINAL AT THE
 SERVICE. NEC 250.94
 10. PER NEC 110.16 ARC FLASH HAZARD WARNING- PROVIDE A
 GENERAL NOTE ON PLANS. SEE VERBIAGE IN CODE.
 11. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL
 FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS
 REGARDING THIS PROJECT.
  
  