| Plan Review Notes For Permit 16080378 |
| Permit Number |
16080378 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-08-27 04:30:15 | 1) THE GAS RISER SHOWS 3/4 INCH METALLIC PIPE AT THE | | | METER . REFER TO 2014 FGC TABLE 402.4 (2) FOR CORRECT | | | SIZING OF THE GAS SYSTEM.AS DRAWN, IT IS UNDERSIZED. | | | 2) SHOW THE LOCATION OF ANY DOORS OR WINDOWS ON THE | | | FLOOR PLAN AND THE DISTANCE FROM THESE OPENINGS TO THE | | | TANKLESS WATER HEATER. COMPLY WITH THE 2014 FGC SEC. | | | 503. | | | | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | |
|