Plan Review Notes
Plan Review Notes For Permit 16080368
Permit Number 16080368
Review Stop B
Sequence Number 3
Notes
Date Text
2016-11-07 10:13:15BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16080368
 ADD: 5800 CORPORATE WAY
 CONT: GEN-X CONSTRUCTION
 TEL: 561-963-4490
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: MON. NOV. 07/ 2016
 ACTION: DENIED
  
 1) COMPLIED. SCOPE OF WORK IS FOR THE 6,000 SQ. FT.
 BUILDING.
  
 2) 3RD REQUEST. FLOOD ELEVATION CERTIFICATE. THE
 SUBMITTED ELEVATION CERTIFICATE DATED 7/12/2016 IS ON
 THE OLD FORMS AND ALSO HAS CHECKED THAT THE FORM IS FOR
 FINISHED CONSTRUCTION, SEE LINE C1. THIS CERTIFICATE
 SHOULD ON LINE C1 BE CHECKED FOR CONSTRUCTION DRAWINGS
 AND INDICATE HOW COMPLIANCE WITH THE REQUIRED 14.5 FEET
 NGVD FOR EITHER FLOOD PROOFING OR THE MINIMUM ELEVATION
 OF 14.5 FEET NGVD FINISH FLOOR WILL BE ACHIEVED.
 THE BUILDING PERMIT SET OF DRAWINGS WILL ALSO REFLECT
 HOW CODE COMPLIANCE WITH 2014 FBC-B 1612.5 FLOOD HAZARD
 DOCUMENTATION.
  
 THE MAIN 6,000 SQUARE FOOT BUILDING WAS BUILT (1976)
 PRE-FIRM (COMMUNITY PANEL NUMBER 120229 0015B EFFECTIVE
 DATE MARCH 01/ 1979) MEANING BEFORE THERE WERE FLOOD
 ELEVATION REQUIREMENTS. PRE FIRM. THIS BUILDING WILL
 HAVE TO MEET THE REQUIREMENTS OF SUBSTANTIAL
 IMPROVEMENTS SINCE THE VALUE OF THE IMPROVEMENT IS 86 %
 OF THE VALUE OF THE IMPROVEMENT VALUE OF THE STRUCTURE.
 FOR NON-RESIDENTIAL STRUCTURES EITHER THE RAISING OF
 THE BUILDING, OR RAISING THE FLOOR OR MEETING THE
 REQUIREMENTS OF DRY-FLOOD PROOFING. PLEASE REVIEW FEMAS
 TECHNICAL BULLETIN 3-93 NON-RESIDENTIAL
 FLOODPROOFING-REQUIREMENTS AND CERTIFICATION FOR
 BUILDINGS LOCATED IN SPECIAL FLOOD HAZARD AREAS IN
 ACCORDANCE WITH THE NATIONAL FLOOD INSURANCE PROGRAM.
 PLEASE SELECT WHICH METHOD OF CODE COMPLIANCE WILL BE
 SELECTED TO ENSURE COMPLIANCE WITH
 2014 FBC-B 1612.5 FLOOD HAZARD DOCUMENTATION.
 107.3.5.1.1. MINIMUM PLAN REVIEW DOCUMENTS (8) FLOOD
 REQUIREMENTS IN ACCORDANCE WITH SECTION 1612, INCLUDING
 LOWEST FLOOR ELEVATIONS, ENCLOSURES, FLOOD
 DAMAGE-RESISTANT MATERIALS.
  
 =======================================================
 ================
 1ST ROUND OF REVIEW COMMENTS. PLEASE NOTE THIS
 STRUCTURE IS BUILT IN AN A8 FLOOD ZONE. FBC BUILDING
 1612 AND CITY OF WPB CODE OF ORDINANCES SECTION 94-546.
 STRUCTURE IS LOCATED IN AN "A8" FLOOD ZONE. A FLOOD
 ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE REVIEW
 CITY ORDINANCE FOR THE CITY REQUIREMENTS REQUIRE AN
 ADDITIONAL 6 INCHES OF ELEVATION. BASE FLOOD FOR THE A8
 FLOOD ZONE IS 14.0 FT. NGVD PLUS AN ADDITIONAL 6 INCH
 FREEBOARD REQUIRED BY AND CITY OF WPB CODE OF
 ORDINANCES SECTION 94-546.
  
 PLEASE NOTE THIS STRUCTURE WILL ALSO HAVE TO MEET THE
 REQUIREMENTS OF SUBSTANTIAL IMPROVEMENTS. THE P.B.C.
 PROPERTY APPRAISERS OFFICE LIST THE VALUE FOR THE
 STRUCTURE AS $489,474.00 THE VALUE OF THE PROJECT IS
 $424,000.00 IN VALUE WELL OVER THE 50 % OF THE VALUE
 FOR THE STRUCTURE. ANY FLOORS AND OR ATTENDANT
 EQUIPMENT PADS WILL NEED TO BE ABOVE THE 14.5 FEET
 NGVD.
  
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT.
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS
 A/C PADS OR OTHER SLABS FOR GENERATORS
 FEMA NEW FORM AVAILABLE JUNE 13/2016.
 OMB NO. 1660-0008
 EXPIRATION DATE: NOV. 30/2018
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 3-7) COMPLIED.
 7) PROVISO: SHEET 08 SHOWS INSULATION LAYING DIRECTLY
 ON DROPPED CEILINGS. (SOUND CONTROL ONLY).
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  