| 2016-11-07 10:13:15 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16080368 |
| | ADD: 5800 CORPORATE WAY |
| | CONT: GEN-X CONSTRUCTION |
| | TEL: 561-963-4490 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: MON. NOV. 07/ 2016 |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. SCOPE OF WORK IS FOR THE 6,000 SQ. FT. |
| | BUILDING. |
| | |
| | 2) 3RD REQUEST. FLOOD ELEVATION CERTIFICATE. THE |
| | SUBMITTED ELEVATION CERTIFICATE DATED 7/12/2016 IS ON |
| | THE OLD FORMS AND ALSO HAS CHECKED THAT THE FORM IS FOR |
| | FINISHED CONSTRUCTION, SEE LINE C1. THIS CERTIFICATE |
| | SHOULD ON LINE C1 BE CHECKED FOR CONSTRUCTION DRAWINGS |
| | AND INDICATE HOW COMPLIANCE WITH THE REQUIRED 14.5 FEET |
| | NGVD FOR EITHER FLOOD PROOFING OR THE MINIMUM ELEVATION |
| | OF 14.5 FEET NGVD FINISH FLOOR WILL BE ACHIEVED. |
| | THE BUILDING PERMIT SET OF DRAWINGS WILL ALSO REFLECT |
| | HOW CODE COMPLIANCE WITH 2014 FBC-B 1612.5 FLOOD HAZARD |
| | DOCUMENTATION. |
| | |
| | THE MAIN 6,000 SQUARE FOOT BUILDING WAS BUILT (1976) |
| | PRE-FIRM (COMMUNITY PANEL NUMBER 120229 0015B EFFECTIVE |
| | DATE MARCH 01/ 1979) MEANING BEFORE THERE WERE FLOOD |
| | ELEVATION REQUIREMENTS. PRE FIRM. THIS BUILDING WILL |
| | HAVE TO MEET THE REQUIREMENTS OF SUBSTANTIAL |
| | IMPROVEMENTS SINCE THE VALUE OF THE IMPROVEMENT IS 86 % |
| | OF THE VALUE OF THE IMPROVEMENT VALUE OF THE STRUCTURE. |
| | FOR NON-RESIDENTIAL STRUCTURES EITHER THE RAISING OF |
| | THE BUILDING, OR RAISING THE FLOOR OR MEETING THE |
| | REQUIREMENTS OF DRY-FLOOD PROOFING. PLEASE REVIEW FEMAS |
| | TECHNICAL BULLETIN 3-93 NON-RESIDENTIAL |
| | FLOODPROOFING-REQUIREMENTS AND CERTIFICATION FOR |
| | BUILDINGS LOCATED IN SPECIAL FLOOD HAZARD AREAS IN |
| | ACCORDANCE WITH THE NATIONAL FLOOD INSURANCE PROGRAM. |
| | PLEASE SELECT WHICH METHOD OF CODE COMPLIANCE WILL BE |
| | SELECTED TO ENSURE COMPLIANCE WITH |
| | 2014 FBC-B 1612.5 FLOOD HAZARD DOCUMENTATION. |
| | 107.3.5.1.1. MINIMUM PLAN REVIEW DOCUMENTS (8) FLOOD |
| | REQUIREMENTS IN ACCORDANCE WITH SECTION 1612, INCLUDING |
| | LOWEST FLOOR ELEVATIONS, ENCLOSURES, FLOOD |
| | DAMAGE-RESISTANT MATERIALS. |
| | |
| | ======================================================= |
| | ================ |
| | 1ST ROUND OF REVIEW COMMENTS. PLEASE NOTE THIS |
| | STRUCTURE IS BUILT IN AN A8 FLOOD ZONE. FBC BUILDING |
| | 1612 AND CITY OF WPB CODE OF ORDINANCES SECTION 94-546. |
| | STRUCTURE IS LOCATED IN AN "A8" FLOOD ZONE. A FLOOD |
| | ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE REVIEW |
| | CITY ORDINANCE FOR THE CITY REQUIREMENTS REQUIRE AN |
| | ADDITIONAL 6 INCHES OF ELEVATION. BASE FLOOD FOR THE A8 |
| | FLOOD ZONE IS 14.0 FT. NGVD PLUS AN ADDITIONAL 6 INCH |
| | FREEBOARD REQUIRED BY AND CITY OF WPB CODE OF |
| | ORDINANCES SECTION 94-546. |
| | |
| | PLEASE NOTE THIS STRUCTURE WILL ALSO HAVE TO MEET THE |
| | REQUIREMENTS OF SUBSTANTIAL IMPROVEMENTS. THE P.B.C. |
| | PROPERTY APPRAISERS OFFICE LIST THE VALUE FOR THE |
| | STRUCTURE AS $489,474.00 THE VALUE OF THE PROJECT IS |
| | $424,000.00 IN VALUE WELL OVER THE 50 % OF THE VALUE |
| | FOR THE STRUCTURE. ANY FLOORS AND OR ATTENDANT |
| | EQUIPMENT PADS WILL NEED TO BE ABOVE THE 14.5 FEET |
| | NGVD. |
| | |
| | DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE |
| | REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES |
| | REQUIRED: |
| | (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE |
| | PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR |
| | HEIGHT. |
| | (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND |
| | ELEVATION CERTIFICATE IS REQUIRED |
| | (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY |
| | OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE |
| | CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR |
| | ATTENDANTS |
| | A/C PADS OR OTHER SLABS FOR GENERATORS |
| | FEMA NEW FORM AVAILABLE JUNE 13/2016. |
| | OMB NO. 1660-0008 |
| | EXPIRATION DATE: NOV. 30/2018 |
| | HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM |
| | |
| | 3-7) COMPLIED. |
| | 7) PROVISO: SHEET 08 SHOWS INSULATION LAYING DIRECTLY |
| | ON DROPPED CEILINGS. (SOUND CONTROL ONLY). |
| | |
| | 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |