| Date |
Text |
| 2016-08-30 09:33:37 | 1) SHT. 00 SHOWS A PROPOSED PROPANE TANK. THE PROPANE |
| | TANK AND ALL ASSOCIATED PIPING SHALL BE SUBMITTED AS A |
| | SEPARATE PERMIT.WPB AMEND. TO FBC SEC. 107.2.1. |
| | 2) SHT.00 - HANDICAPPED ACCESSIBILITY REQS. - NOTE #1 - |
| | THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE |
| | GRIPPING SURFACE PER 2014 FAC SEC. 609.4. |
| | 3) NOTE #2 - THE GRAB BAR BEHIND THE WATER CLOSET SHALL |
| | COMPLY WITH 2014 FAC SEC.604.5.2 AND FIGURE 604.5.2. IF |
| | THE GRAB BAR IS 36 INCHES LONG, IT SHALL NOT BE |
| | CENTERED ON THE FIXTURE.SEE SHT. 03 ALSO. |
| | 4) NOTE #4 - THE TOILET PAPER DISPENSER SHALL BE |
| | LOCATED IN ACCORDANCCE WITH FAC SEC.604.7.SEE SHT. 03 |
| | ALSO. |
| | 5) THE PLANS INCLUDE AN OUT BUILDING THAT IS NOT SHOWN |
| | ON THE SITE PLAN. SUBMIT A SITE PLAN SHOWING THIS |
| | BUILDING AND THE SCOPE OF WORK TO BE DONE IN THIS |
| | BUILDING. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 6) THE FIGURES SHOWN FOR THE ACCESSIBILITY REQUIREMENTS |
| | ARE NOT INCLUDED IN THE 2014 FAC. CLARIFY. |
| | 7) THE SINK IN THE EMPLOYEE LOUNGE SHALL COMPLY WITH |
| | 2014 FAC SEC. 212.1 & 606. |
| | 8) SHOW THE WIDTH OF THE TOILET ROOMS NEAR THE JANITOR |
| | ROOM. COMPLY WITH THE CLEAR FLOOR SPACE REQUIRED FOR |
| | THE WATER CLOSET AND LAVATORY. FAC SEC.604.3 & 606. |
| | 9) THE NUMBER OF ACCESSIBLE SINKS SHALL COMPLY WITH FAC |
| | SEC.212.3. CLEARLY IDENTIFY THE HANDICAPPED ACCESSIBLE |
| | SINKS ON THE PLAN. |
| | 10) SHT. 04 - CODE BOX SHOWS THE OCCUPANCY OF THIS |
| | SPACE AS AN A-2 AND THE HEIGHT AND BUILDING AREA BOX |
| | NOTES THE OCCUPANCY AS A "B" OCCUPANCY. INDICATE THE |
| | CORRECT OCCUPANCY ON THE PLANS IN ACCORDANCE WITH THE |
| | 2014 FBC SEC.303.3. |
| | 11) DRINKING FOUNTAINS ARE REQUIRED IN THIS FACILITY IN |
| | ACCORDANCE WITH TABLE 403.1 OF THE 2014 FPC. A MINIMUM |
| | OF TWO DRINKING FOUNTAINS COMPLYING WITH FAC SEC.211 |
| | ARE REQUIRED. |
| | 12) THE TWO WATER CLOSETS AND THE MOP SINK ARE NOT |
| | PROPERLY VENTED AND THE MOP SINK CANNOT BE INSTALLED ON |
| | A WET VENT AS IT IS NOT A FIXTURE IN A BATHROOM GROUP |
| | PER THE 2014 FPC SEC.912.1. |
| | 13) INDICATE THE SIZE OF THE "ACCEPTANCE TANK" ON THE |
| | PLANS. |
| | 14) SHT. P-5 SHOWS A CIRCULATION PUMP. SHOW THIS ON THE |
| | WATER RISER . IF THIS PUMP IS FOR THE HOT WATER |
| | RECIRCULATION SYSTEM, CLEARLY IDENTIFY ALL THE LINES |
| | AND SUBMIT A COMPLETE PIPING DETAIL FOR THE |
| | RECIRCULATION SYSTEM INCLUDING THE WATER HEATTER. WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 15) THE RECIRCULATION SYSTEM SHALL COMPLY WITHTHE 2014 |
| | FPC SEC.607.2.2. |
| | 16) IS THERE ANY MEDICAL GAS BEING INSTALLED IN THIS |
| | FACILITY? IF SO, SUBMIT COMPLETE PIPING RISER AND FLOOR |
| | PLAN. |
| | 17) WHAT TYPE OF MEDICAL CARE FACILITY IS THIS? IS IT |
| | AN AMBULATORY CARE FACILITY ( FBC SEC.422 ) OR AN |
| | OFFICE SURGERY SUITE ( FBC 469 ). |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |