Plan Review Notes
Plan Review Notes For Permit 16080368
Permit Number 16080368
Review Stop P
Sequence Number 1
Notes
Date Text
2016-08-30 09:33:371) SHT. 00 SHOWS A PROPOSED PROPANE TANK. THE PROPANE
 TANK AND ALL ASSOCIATED PIPING SHALL BE SUBMITTED AS A
 SEPARATE PERMIT.WPB AMEND. TO FBC SEC. 107.2.1.
 2) SHT.00 - HANDICAPPED ACCESSIBILITY REQS. - NOTE #1 -
 THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE PER 2014 FAC SEC. 609.4.
 3) NOTE #2 - THE GRAB BAR BEHIND THE WATER CLOSET SHALL
 COMPLY WITH 2014 FAC SEC.604.5.2 AND FIGURE 604.5.2. IF
 THE GRAB BAR IS 36 INCHES LONG, IT SHALL NOT BE
 CENTERED ON THE FIXTURE.SEE SHT. 03 ALSO.
 4) NOTE #4 - THE TOILET PAPER DISPENSER SHALL BE
 LOCATED IN ACCORDANCCE WITH FAC SEC.604.7.SEE SHT. 03
 ALSO.
 5) THE PLANS INCLUDE AN OUT BUILDING THAT IS NOT SHOWN
 ON THE SITE PLAN. SUBMIT A SITE PLAN SHOWING THIS
 BUILDING AND THE SCOPE OF WORK TO BE DONE IN THIS
 BUILDING. WPB AMEND. TO FBC SEC. 107.2.1.
 6) THE FIGURES SHOWN FOR THE ACCESSIBILITY REQUIREMENTS
 ARE NOT INCLUDED IN THE 2014 FAC. CLARIFY.
 7) THE SINK IN THE EMPLOYEE LOUNGE SHALL COMPLY WITH
 2014 FAC SEC. 212.1 & 606.
 8) SHOW THE WIDTH OF THE TOILET ROOMS NEAR THE JANITOR
 ROOM. COMPLY WITH THE CLEAR FLOOR SPACE REQUIRED FOR
 THE WATER CLOSET AND LAVATORY. FAC SEC.604.3 & 606.
 9) THE NUMBER OF ACCESSIBLE SINKS SHALL COMPLY WITH FAC
 SEC.212.3. CLEARLY IDENTIFY THE HANDICAPPED ACCESSIBLE
 SINKS ON THE PLAN.
 10) SHT. 04 - CODE BOX SHOWS THE OCCUPANCY OF THIS
 SPACE AS AN A-2 AND THE HEIGHT AND BUILDING AREA BOX
 NOTES THE OCCUPANCY AS A "B" OCCUPANCY. INDICATE THE
 CORRECT OCCUPANCY ON THE PLANS IN ACCORDANCE WITH THE
 2014 FBC SEC.303.3.
 11) DRINKING FOUNTAINS ARE REQUIRED IN THIS FACILITY IN
 ACCORDANCE WITH TABLE 403.1 OF THE 2014 FPC. A MINIMUM
 OF TWO DRINKING FOUNTAINS COMPLYING WITH FAC SEC.211
 ARE REQUIRED.
 12) THE TWO WATER CLOSETS AND THE MOP SINK ARE NOT
 PROPERLY VENTED AND THE MOP SINK CANNOT BE INSTALLED ON
 A WET VENT AS IT IS NOT A FIXTURE IN A BATHROOM GROUP
 PER THE 2014 FPC SEC.912.1.
 13) INDICATE THE SIZE OF THE "ACCEPTANCE TANK" ON THE
 PLANS.
 14) SHT. P-5 SHOWS A CIRCULATION PUMP. SHOW THIS ON THE
 WATER RISER . IF THIS PUMP IS FOR THE HOT WATER
 RECIRCULATION SYSTEM, CLEARLY IDENTIFY ALL THE LINES
 AND SUBMIT A COMPLETE PIPING DETAIL FOR THE
 RECIRCULATION SYSTEM INCLUDING THE WATER HEATTER. WPB
 AMEND. TO FBC SEC. 107.2.1.
 15) THE RECIRCULATION SYSTEM SHALL COMPLY WITHTHE 2014
 FPC SEC.607.2.2.
 16) IS THERE ANY MEDICAL GAS BEING INSTALLED IN THIS
 FACILITY? IF SO, SUBMIT COMPLETE PIPING RISER AND FLOOR
 PLAN.
 17) WHAT TYPE OF MEDICAL CARE FACILITY IS THIS? IS IT
 AN AMBULATORY CARE FACILITY ( FBC SEC.422 ) OR AN
 OFFICE SURGERY SUITE ( FBC 469 ).
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved