Plan Review Notes
Plan Review Notes For Permit 16080368
Permit Number 16080368
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-08-19 11:07:36THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET 00 - A "NEW PROPANE TANK" IS INDICATED BY
 DIAGRAM. A PROPANE TANK INSTALLATION IS NOT APPROVED
 UNDER THIS PERMIT.
  
 THE PROPANE TANK INSTALLATION SHALL BE UNDER SEPARATE
 PERMIT. PLEASE PROVIDE A CLOUDED NOTE ON RESUBMITAL.
  
  
  
 2) SHEET 04 - THE OCCUPANCY IS INDICATED AS ASSEMBLY IN
 ONE AREA AND BUSINESS IN ANOTHER. THIS PROPOSED PROJECT
 APPEARS TO BE AN OCCUPANCY CHANGE FROM BUSINESS TO
 AMBULATORY HEALTHCARE ACCORDING TO THE FLORIDA FIRE
 PREVENTION CODE.
  
 NFPA 101, 5TH EDITION
 3.3.188 OCCUPANCY. THE PURPOSE FOR WHICH A BUILDING OR
 OTHER STRUCTURE, OR PART THEREOF, IS USED OR INTENDED
 TO BE USED. [ASCE/SEI 7:1.2]
 3.3.188.1* AMBULATORY HEALTH CARE OCCUPANCY. AN
 OCCUPANCY USED TO PROVIDE SERVICES OR TREATMENT
 SIMULTANEOUSLY TO FOUR OR MORE PATIENTS THAT PROVIDES,
 ON AN OUTPATIENT BASIS, ONE OR MORE OF THE FOLLOWING:
 (1) TREATMENT FOR PATIENTS THAT
 RENDERS THE PATIENTS INCAPABLE OF TAKING ACTION FOR
 SELFPRESERVATION UNDER EMERGENCY CONDITIONS WITHOUT THE
 ASSISTANCE OF OTHERS; (2) ANESTHESIA THAT RENDERS THE
 PATIENTS INCAPABLE OF TAKING ACTION FOR
 SELF-PRESERVATION UNDER EMERGENCY CONDITIONS WITHOUT
 THE ASSISTANCE OF OTHERS; (3) EMERGENCY OR URGENT CARE
 FOR PATIENTS WHO, DUE TO THE NATURE OF THEIR INJURY OR
 ILLNESS, ARE INCAPABLE OF TAKING ACTION FOR
 SELF-PRESERVATION UNDER EMERGENCY CONDITIONS WITHOUT
 THE ASSISTANCE OF OTHERS.
  
 PLEASE REVIEW AND CORRECT AND ENSURE THIS PROJECT MEETS
 THE APPLICABLE CODE REQUIREMENTS.
  
  
  
 3) SHEET 04 - THERE IS NO INDICATION OF ANY EXISTING
 FIRE SPRINKLER AND/OR FIRE ALARM SYSTEM.
  
 SHEET FS 1 INDICATES THE INSTALLATION OF A FIRE
 SPRINKLER SYSTEM; HOWEVER THERE IS NO INDICATION OF A
 FIRE ALARM.
  
 NFPA 101, CHAPTER 20 NEW AMBULATORY HEATH CARE
 OCCUPANCIES
  
 20.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 20.3.4.1 GENERAL. AMBULATORY HEALTH CARE FACILITIES
 SHALL BE PROVIDED WITH FIRE ALARM SYSTEMS IN ACCORDANCE
 WITH SECTION 9.6, EXCEPT AS MODIFIED BY 20.3.4.2
 THROUGH 20.3.4.4.
  
 ANY EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR
 FIRE SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
  
 PLEASE PROVIDE INDICATIONS AS APPLICABLE.
  
  
  
 4) SHEET 04 - THERE APPEARS TO BE MISSING EXIT SIGNAGE
 AT THE END OF THE CORRIDOR BY THE EMPLOYEE LOUNGE AND
 IN THE CORRIDOR AT THE DOORS TO THE WAITING ROOM.
  
 7.10.1.2 EXITS.
 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS
 THAT OBVIOUSLY AND CLEARLY ARE IDENTIFIABLE AS EXITS,
 SHALL BE MARKED BY AN APPROVED SIGN THAT IS READILY
 VISIBLE FROM ANY DIRECTION OF EXIT ACCESS.
  
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 5) SHEET 04 - THERE DOES NOT APPEAR TO BE ANY EMERGENCY
 LIGHTING IN THE CORRIDORS.
  
 7.8 ILLUMINATION OF MEANS OF EGRESS.
 7.8.1 GENERAL.
 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTION 7.8 FOR EVERY
 BUILDING AND STRUCTURE WHERE REQUIRED IN CHAPTERS 11
 THROUGH 43. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT
 ACCESS SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCALATORS, AND PASSAGEWAYS LEADING
 TO AN EXIT. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT
 DISCHARGE SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCALATORS, WALKWAYS, AND EXIT
 PASSAGEWAYS LEADING TO A PUBLIC WAY.
 7.8.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL BE
 CONTINUOUS DURING THE TIME THAT THE CONDITIONS OF
 OCCUPANCY REQUIRE THAT THE MEANS OF EGRESS BE AVAILABLE
 FOR USE, UNLESS OTHERWISE PROVIDED IN7.8.1.2.2.
 7.9 EMERGENCY LIGHTING.
 7.9.1 GENERAL.
 7.9.1.1* EMERGENCY LIGHTING FACILITIES FOR MEANS OF
 EGRESS SHALL BE PROVIDED IN ACCORDANCE WITH SECTION 7.9
 FOR THE FOLLOWING:
 (1) BUILDINGS OR STRUCTURES WHERE REQUIRED IN CHAPTERS
 11 THROUGH 43
 7.9.2 PERFORMANCE OF SYSTEM.
 7.9.2.1* EMERGENCY ILLUMINATION SHALL BE PROVIDED FOR A
 MINIMUM OF 1? HOURS IN THE EVENT OF FAILURE OF NORMAL
 LIGHTING. EMERGENCY LIGHTING FACILITIES SHALL BE
 ARRANGED TO PROVIDE INITIAL ILLUMINATION THAT IS NOT
 LESS THAN AN AVERAGE OF 1 FT-CANDLE (10.8 LUX) AND, AT
 ANY POINT, NOT LESS THAN 0.1 FT-CANDLE (1.1 LUX),
 MEASURED ALONG THE PATH OF EGRESS AT FLOOR LEVEL.
 ILLUMINATION LEVELS SHALL BE PERMITTED TO DECLINE TO
 NOT LESS THAN AN AVERAGE OF 0.6 FT-CANDLE (6.5 LUX)
 AND, AT ANY POINT, NOT LESS THAN 0.06 FT-CANDLE (0.65
 LUX) AT THE END OF 1? HOURS. A MAXIMUM-TO-MINIMUM
 ILLUMINATION UNIFORMITY RATIO OF 40 TO 1 SHALL NOT BE
 EXCEEDED.
  
  
 PLEASE REVIEW AND CORRECT.
  
  