Plan Review Notes
Plan Review Notes For Permit 16080368
Permit Number 16080368
Review Stop E
Sequence Number 1
Notes
Date Text
2016-08-16 10:50:28ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 PROJECT NAME: PALM BEACH SPINE & DIAGNOSTICS, LLC
 JOB ADDRESS: 5800 CORPORATE WAY
 DESCRIPTION: INTERIOR BUILD-OUT AND MAIN BLDG.
 RENOVATION ONLY
 MASTER PERMIT: 16080368
  
 BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS.
 ADDITIONAL CORRECTIONS MAY BE REQUIRED BY FIRE AND
 AFTER REVIEW OF SUBMITTED CORRECTIONS.
  
 1. FBC-B 107.2.1: NOTE 1 HAS TO BE SPECIFIC TO THE
 APPLICABLE CODE. (NEC 2011)
 2. NOTE 7 CORRECTION: IT IS THE AMBIENT CONDITIONS AND
 NOT THE WIRE GAGE THAT DETERMINES INSULATION
 REQUIREMENTS.
 3. CORRECT ELECTRICAL SYMBOLS LEGEND TO DIFFERENTIATE
 BETWEEN WALL & CEILING MOUNTED EXIT LIGHTS.
 4. NEC 600.5: EACH COMMERCIAL BUILDING AND EACH
 COMMERCIAL OCCUPANCY ACCESSIBLE TO PEDESTRIANS SHALL BE
 PROVIDED WITH AT LEAST ONE 20 AMP DEDICATED OUTLET IN
 AN ACCESSIBLE LOCATION AT EACH ENTRANCE TO EACH TENANT
 SPACE FOR SIGN OR OUTLINE LIGHTING. SERVICE HALLWAYS OR
 CORRIDORS SHALL NOT BE CONSIDERED ACCESSIBLE TO
 PEDESTRIANS. NONE OF THE THREE DOORS COMPLY.
 5. FBC-E 405.7.1: AT THE LEAST 50% OF ALL 125-VOLT, 15-
 AND 20-AMPERE RECEPTACLES SHALL BE AUTOMATICALLY
 CONTROLLED WHERE INSTALLED IN PRIVATE OFFICES, OPEN
 OFFICES, AND COMPUTER CLASSROOMS. THIS INCLUDES THOSE
 INSTALLED IN MODULAR PARTITIONS. (SEE ASHRAE STANDARD
 90.1)
 6. GENERAL NOTES ON PG. E 2 REFERENCE CODE CORRECTION
 NEC 150.118.
 7. FBC-B 1011.1 EXITS AND EXIT ACCESS SHALL BE MARKED
 BY AN APPROVED EXIT SIGN READILY VISIBLE FROM ANY
 DIRECTION OF EGRESS TRAVEL. THE PATH OF EGRESS SHALL BE
 CLEARLY MARKED WHEN NOT READILY VISIBLE. THERE SHALL
 NOT BE MORE 100? BETWEEN EXIT SIGN ALONG THE PATH OF
 EGRESS. THE SUBMITTED PLANS ONLY HAVE EXIT SIGNAGE AT
 THE DOORS.
 8. FBC-B1006.1: THE MEANS OF EGRESS, INCLUDING THE EXIT
 DISCHARGE, SHALL BE ILLUMINATED AT ALL TIMES THE
 BUILDING SPACE SERVED BY THE MEANS OF EGRESS ARE
 OCCUPIED. PROVIDE A BETTER DETAILED SITE DRAWING
 SHOWING LIGHTING FOR THE EXIT DISCHARGE.
 9. NEC 410 IV: PROVIDE LUMINAIRE SUPPORT DIAGRAMS
 COMPLIANT WITH THIS SECTION.
 10. FBC-E C402.4.8: RECESSED LIGHTING INSTALLED IN THE
 BUILDING THERMAL ENVELOPE SHALL BE IC RATED AND BE
 SEALED TO LIMIT AIR LEAKAGE BETWEEN CONDITIONED &
 UNCONDITIONED SPACES.
 11. IDENTIFY THE EXIT LIGHT SYMBOL IN THE ELECTRICAL
 RISER DIAGRAM.
 12. YOU SHALL BE MORE SPECIFIC AS TO THE TYPE OF
 PROCEDURES CONDUCTED TO BETTER DETERMINE THE EXTENT OF
 EMERGENCY POWER SOURCE REQUIREMENTS. NO EMERGENCY POWER
 IS CURRENTLY INDICTED ON THE RISER DIAGRAM.
 13. YOU SHALL ALSO INDICATE THE TYPE OF ANESTHETICS
 USED TO FURTHER DETERMINE THE EMERGENCY POWER
 REQUIREMENTS.
 14. ALL WIRING IN THE PATIENT CARE AREAS SHALL COMPLY
 WITH EVERY REQUIREMENT OF NEC 517.13(A) & (B).
 15. EACH PATIENT CARE BED TO COMPLY WITH NEC 517.18.
 16. AS MENTIONED ABOVE, YOU ARE TO PROVIDE AN
 ALTERNATIVE POWER SOURCE AS DETERMINED BY THE EXTENT OF
 SERVICES PROVIDED. AT THE MOMENT IS APPEARS THAT AN
 ESSENTIAL POWER SOURCE AS DESCRIBED IN NEC 517.41
 SHOULD BE SUFFICIENT.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  
  