| 2016-08-16 10:50:28 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | PROJECT NAME: PALM BEACH SPINE & DIAGNOSTICS, LLC |
| | JOB ADDRESS: 5800 CORPORATE WAY |
| | DESCRIPTION: INTERIOR BUILD-OUT AND MAIN BLDG. |
| | RENOVATION ONLY |
| | MASTER PERMIT: 16080368 |
| | |
| | BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS. |
| | ADDITIONAL CORRECTIONS MAY BE REQUIRED BY FIRE AND |
| | AFTER REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. FBC-B 107.2.1: NOTE 1 HAS TO BE SPECIFIC TO THE |
| | APPLICABLE CODE. (NEC 2011) |
| | 2. NOTE 7 CORRECTION: IT IS THE AMBIENT CONDITIONS AND |
| | NOT THE WIRE GAGE THAT DETERMINES INSULATION |
| | REQUIREMENTS. |
| | 3. CORRECT ELECTRICAL SYMBOLS LEGEND TO DIFFERENTIATE |
| | BETWEEN WALL & CEILING MOUNTED EXIT LIGHTS. |
| | 4. NEC 600.5: EACH COMMERCIAL BUILDING AND EACH |
| | COMMERCIAL OCCUPANCY ACCESSIBLE TO PEDESTRIANS SHALL BE |
| | PROVIDED WITH AT LEAST ONE 20 AMP DEDICATED OUTLET IN |
| | AN ACCESSIBLE LOCATION AT EACH ENTRANCE TO EACH TENANT |
| | SPACE FOR SIGN OR OUTLINE LIGHTING. SERVICE HALLWAYS OR |
| | CORRIDORS SHALL NOT BE CONSIDERED ACCESSIBLE TO |
| | PEDESTRIANS. NONE OF THE THREE DOORS COMPLY. |
| | 5. FBC-E 405.7.1: AT THE LEAST 50% OF ALL 125-VOLT, 15- |
| | AND 20-AMPERE RECEPTACLES SHALL BE AUTOMATICALLY |
| | CONTROLLED WHERE INSTALLED IN PRIVATE OFFICES, OPEN |
| | OFFICES, AND COMPUTER CLASSROOMS. THIS INCLUDES THOSE |
| | INSTALLED IN MODULAR PARTITIONS. (SEE ASHRAE STANDARD |
| | 90.1) |
| | 6. GENERAL NOTES ON PG. E 2 REFERENCE CODE CORRECTION |
| | NEC 150.118. |
| | 7. FBC-B 1011.1 EXITS AND EXIT ACCESS SHALL BE MARKED |
| | BY AN APPROVED EXIT SIGN READILY VISIBLE FROM ANY |
| | DIRECTION OF EGRESS TRAVEL. THE PATH OF EGRESS SHALL BE |
| | CLEARLY MARKED WHEN NOT READILY VISIBLE. THERE SHALL |
| | NOT BE MORE 100? BETWEEN EXIT SIGN ALONG THE PATH OF |
| | EGRESS. THE SUBMITTED PLANS ONLY HAVE EXIT SIGNAGE AT |
| | THE DOORS. |
| | 8. FBC-B1006.1: THE MEANS OF EGRESS, INCLUDING THE EXIT |
| | DISCHARGE, SHALL BE ILLUMINATED AT ALL TIMES THE |
| | BUILDING SPACE SERVED BY THE MEANS OF EGRESS ARE |
| | OCCUPIED. PROVIDE A BETTER DETAILED SITE DRAWING |
| | SHOWING LIGHTING FOR THE EXIT DISCHARGE. |
| | 9. NEC 410 IV: PROVIDE LUMINAIRE SUPPORT DIAGRAMS |
| | COMPLIANT WITH THIS SECTION. |
| | 10. FBC-E C402.4.8: RECESSED LIGHTING INSTALLED IN THE |
| | BUILDING THERMAL ENVELOPE SHALL BE IC RATED AND BE |
| | SEALED TO LIMIT AIR LEAKAGE BETWEEN CONDITIONED & |
| | UNCONDITIONED SPACES. |
| | 11. IDENTIFY THE EXIT LIGHT SYMBOL IN THE ELECTRICAL |
| | RISER DIAGRAM. |
| | 12. YOU SHALL BE MORE SPECIFIC AS TO THE TYPE OF |
| | PROCEDURES CONDUCTED TO BETTER DETERMINE THE EXTENT OF |
| | EMERGENCY POWER SOURCE REQUIREMENTS. NO EMERGENCY POWER |
| | IS CURRENTLY INDICTED ON THE RISER DIAGRAM. |
| | 13. YOU SHALL ALSO INDICATE THE TYPE OF ANESTHETICS |
| | USED TO FURTHER DETERMINE THE EMERGENCY POWER |
| | REQUIREMENTS. |
| | 14. ALL WIRING IN THE PATIENT CARE AREAS SHALL COMPLY |
| | WITH EVERY REQUIREMENT OF NEC 517.13(A) & (B). |
| | 15. EACH PATIENT CARE BED TO COMPLY WITH NEC 517.18. |
| | 16. AS MENTIONED ABOVE, YOU ARE TO PROVIDE AN |
| | ALTERNATIVE POWER SOURCE AS DETERMINED BY THE EXTENT OF |
| | SERVICES PROVIDED. AT THE MOMENT IS APPEARS THAT AN |
| | ESSENTIAL POWER SOURCE AS DESCRIBED IN NEC 517.41 |
| | SHOULD BE SUFFICIENT. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |