2016-08-11 14:28:38REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 - CLARIFY NEC STANDARD BEING USED WERE CURRENTLY IN
 2011 VERSION. ADD A NOTE
  
 - PROVIDE A COMPLETE ONE-LINE DIAGRAM SHOWING HOW THE
 INTERCONNECTION IS BEING MADE TO THE ELECTRICAL
 DISTRUBUTION SYSTEM. IF ITS BEING TAPPED OFF THE SUPPLY
 SIDE OF THE SERVICE PLEASE REFLECT WHAT TYPE OF
 ENCLOSURE, HOW THE CONNECTION IS MECHANICALLY BEING
 TAPPED AS FAR AS WITH UL LISTED LUGS, POLARIS OR ANY
 OTHER METHOD ACCEPTABLE AND SERVICE EQUIPMENT SHALL BE
 SUITABLE TO HANDLE AVALIABLE FAULT CURRENTS AND SHORT
 CIRCUIT RATINGS . IF ITS BEING TAPPED OF THE LOAD SIDE
 REFLECT COMPLIANCE WITH PANEL BOARD BUS RATING
 LIMITATIONS, FEEDER TAP RULES, AND CICUIT BREAKERS MUST
 BE SUITABLE FOR BACKFEEDING IF NOT MARKED LINE & LOAD.
 NEC 215.5 & NEC 705.12
  
 - PROVIDE MANUFACTURE SPECS OF SOLAR MODULES, ARRAY
 GROUNDING AND BONDING FITTINGS, AND INVERTER. FBC 107
  
 - FBC 107 BUILDING PLANS SHALL BE DRWAN TO A MINIMUM
 1/8'' SCALE FOR THE QUALITY OF REVIEW.
  
 - THE SITE PLANS TO INCLUDE A DIRECTORY FOR AC & PV
 DISCONNECTING MEANS AT THE SERVICE DENOTING ALL
 LOCATIONS IN THE BUILDING.NEC 690.4(H) MULTIPLE
 INVERTERS.
  
 - PER FAC RULE 61G-15.021. A SEPERATE ELECTRICAL PERMIT
 BY A LICENSED ELECTRICAL CONTRACTOR IS REQUIRED FOR THE
 CONNECTION TO THE PREMISES INTERGAL WIRING OR UTILITY
 SERVICE. SOLAR CONTRACTORS ( CVC ) ARE LIMITED TO
 CONTROL WIRING IN PV SOURCE CIRCUIT, PV OUTPUT CIRCUIT,
 AND THE PV SUPPLY SIDE OF THE POWER CONDITIONING UNIT.