Plan Review Notes
Plan Review Notes For Permit 16080345
Permit Number 16080345
Review Stop E
Sequence Number 1
Notes
Date Text
2016-08-12 09:12:45ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 PROJECT NAME: 801 BRADLEY
 JOB ADDRESS: 801 BRADLEY
 DESCRIPTION: REMODEL UNITS 1, 2 & 3 PER PLANS,
 INCLUDING ELECTRIC, & PLUMBING
 MASTER PERMIT: 16080345
  
 BELOW ARE COMMENTS RELATED TO THE FAILED ELECTRICAL
 REVIEW:
  
 1. YOU SHALL PROVIDE A SITE PLAN SHOWING THE PHYSICAL
 LOCATION OF EACH UNIT IN QUESTION WITH RELATION TO EACH
 OTHER.
 A. FBC-RE3601.2 (NEC 230.2) PERMITS A SINGLE SERVICE
 PER STRUCTURE AND THE ELECTRICAL PLANS AS SUBMITTED
 SHOW AN INDEPENDENT SERVICE FOR EACH UNIT. IF ANY OF
 THE UNITS IS ATTACHED TO THE OTHER, THE STRUCTURE CAN
 ONLY BE SERVED BY A SINGLE SERVICE.
 B. FBC-RE3601.7 (NEC 230.72) REQUIRES THAT ALL
 DISCONNECTS BE GROUPED.
 2. FBC-RE3609.3 (NEC 250.94) REQUIRES THAT YOU PROVIDE
 AN INTER-SYSTEM BONDING TERMINAL AT THE SERVICE. THE
 SERVICE RISERS PROVIDED ARE LACKING THIS.
 3. FBC-R 303.9 REQUIRES THAT YOU PROVIDE HEAT TO
 MAINTAIN 68 DEGREES IN ALL HABITABLE ROOMS WITHIN 3?
 FROM THE FLOOR. YOU INDICATE THAT YOU ARE PROVIDING
 FOUR WALL UNIT AIR CONDITIONERS IN EACH UNIT BUT FAIL
 TO INDICATE OF THE UNITS ARE REVERSE CYCLE AND IF THEY
 ARE THE INDIVIDUAL LOADS INDICATED ON THE PANEL
 SCHEDULE DO NOT REFLECT THAT.
 4. FBC-RE3901.7 (NEC 210.52(E)(3)) REQUIRES THAT THERE
 BE A GFCI PROTECTED OUTLET AT EVERY PORCH OR BALCONY.
 THE ELECTRICAL LAYOUT OF UNIT FAILS TO SHOW THIS.
 5. FBC-RE3903.4 (NEC 210.70(A)) REQUIRES THAT THERE BE
 A LIGHT CONTROLLED BY A WALL SWITCH IN THE LAUNDRY ROOM
 OF UNIT 3 AS WELL AS ON THE OUTSIDE OF THE LAUNDRY ROOM
 DOOR.
 6. THE MISSING SITE PLAN MAKES IT DIFFICULT TO
 DETERMINE THE USUAL POINT OF ENTRY FOR EACH UNIT. THE
 LIGHTING CONTROL SHALL BE AT THE USUAL POINT OF ENTRY.
 VERIFY LIGHTING CONTROL FOR UNIT 2.
 7. FBC-RE3703.3 (NEC 210.52(F)) REQUIRES THAT THERE BE
 A LAUNDRY ROOM CIRCUIT IN EVERY DWELLING UNIT. YOU FAIL
 TO SHOW THIS FOR UNIT 2.
 8. FBC-ER404.1 REQUIRES THAT A MINIMUM OF 75% OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75% OF THE
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN
 ONLY HIGH EFFICIENCY LAMPS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER