| 2016-08-12 09:12:45 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | PROJECT NAME: 801 BRADLEY |
| | JOB ADDRESS: 801 BRADLEY |
| | DESCRIPTION: REMODEL UNITS 1, 2 & 3 PER PLANS, |
| | INCLUDING ELECTRIC, & PLUMBING |
| | MASTER PERMIT: 16080345 |
| | |
| | BELOW ARE COMMENTS RELATED TO THE FAILED ELECTRICAL |
| | REVIEW: |
| | |
| | 1. YOU SHALL PROVIDE A SITE PLAN SHOWING THE PHYSICAL |
| | LOCATION OF EACH UNIT IN QUESTION WITH RELATION TO EACH |
| | OTHER. |
| | A. FBC-RE3601.2 (NEC 230.2) PERMITS A SINGLE SERVICE |
| | PER STRUCTURE AND THE ELECTRICAL PLANS AS SUBMITTED |
| | SHOW AN INDEPENDENT SERVICE FOR EACH UNIT. IF ANY OF |
| | THE UNITS IS ATTACHED TO THE OTHER, THE STRUCTURE CAN |
| | ONLY BE SERVED BY A SINGLE SERVICE. |
| | B. FBC-RE3601.7 (NEC 230.72) REQUIRES THAT ALL |
| | DISCONNECTS BE GROUPED. |
| | 2. FBC-RE3609.3 (NEC 250.94) REQUIRES THAT YOU PROVIDE |
| | AN INTER-SYSTEM BONDING TERMINAL AT THE SERVICE. THE |
| | SERVICE RISERS PROVIDED ARE LACKING THIS. |
| | 3. FBC-R 303.9 REQUIRES THAT YOU PROVIDE HEAT TO |
| | MAINTAIN 68 DEGREES IN ALL HABITABLE ROOMS WITHIN 3? |
| | FROM THE FLOOR. YOU INDICATE THAT YOU ARE PROVIDING |
| | FOUR WALL UNIT AIR CONDITIONERS IN EACH UNIT BUT FAIL |
| | TO INDICATE OF THE UNITS ARE REVERSE CYCLE AND IF THEY |
| | ARE THE INDIVIDUAL LOADS INDICATED ON THE PANEL |
| | SCHEDULE DO NOT REFLECT THAT. |
| | 4. FBC-RE3901.7 (NEC 210.52(E)(3)) REQUIRES THAT THERE |
| | BE A GFCI PROTECTED OUTLET AT EVERY PORCH OR BALCONY. |
| | THE ELECTRICAL LAYOUT OF UNIT FAILS TO SHOW THIS. |
| | 5. FBC-RE3903.4 (NEC 210.70(A)) REQUIRES THAT THERE BE |
| | A LIGHT CONTROLLED BY A WALL SWITCH IN THE LAUNDRY ROOM |
| | OF UNIT 3 AS WELL AS ON THE OUTSIDE OF THE LAUNDRY ROOM |
| | DOOR. |
| | 6. THE MISSING SITE PLAN MAKES IT DIFFICULT TO |
| | DETERMINE THE USUAL POINT OF ENTRY FOR EACH UNIT. THE |
| | LIGHTING CONTROL SHALL BE AT THE USUAL POINT OF ENTRY. |
| | VERIFY LIGHTING CONTROL FOR UNIT 2. |
| | 7. FBC-RE3703.3 (NEC 210.52(F)) REQUIRES THAT THERE BE |
| | A LAUNDRY ROOM CIRCUIT IN EVERY DWELLING UNIT. YOU FAIL |
| | TO SHOW THIS FOR UNIT 2. |
| | 8. FBC-ER404.1 REQUIRES THAT A MINIMUM OF 75% OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75% OF THE |
| | PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN |
| | ONLY HIGH EFFICIENCY LAMPS. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |