| 2016-10-04 07:58:08 | 2ND ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | PROJECT NAME: SACCO RESIDENCE |
| | JOB ADDRESS: 836 ARDMORE ROAD |
| | DESCRIPTION: PARTIAL REWIRE OF HOUSE. |
| | MASTER PERMIT: 1608032 |
| | |
| | BELOW PLEASE FIND A LIST OF ADDITIONAL CORRECTIONS TO |
| | THE PLANS. |
| | |
| | 1. SECTION 107.2.1 OF THE WPB CITY AMENDMENTS TO THE |
| | FBC-B REQUIRES THAT THE CONSTRUCTION DOCUMENTS BE DRAWN |
| | TO A MINIMUM OF 1/8" SCALE. PLEASE INDICATE THE SCALE |
| | TO WHICH THESE DRAWING WERE CREATED. |
| | 2. THE WORD ROMEX AS USED IN THIS NOTE IS TO IDENTIFY A |
| | TYPE OF CABLE. ROMEX IS A BRAND NAME AND NOT A TYPE OF |
| | CABLE, REFER TO CABLE TYPES NM, NMC OR NMS. |
| | 3. YOU WERE ASKED ONCE BEFORE TO INCLUDE/DESCRIBE YOUR |
| | SCOPE OF WORK ON THE PLANS. THIS IS A REQUIREMENT OF |
| | THE CODE AS WELL AS A TOOL FOR THE FIELD INSPECTOR TO |
| | SEE WHAT HAS BEEN APPROVED. |
| | 4. FBC-RE3406.5: ILLUMINATION SHALL BE PROVIDED FOR ALL |
| | WORKING SPACES ABOUT SERVICE EQUIPMENT, SWITCHBOARDS, |
| | AND PANELBOARDS. THIS LIGHT SHALL NOT BE CONTROLLED BY |
| | AUTOMATIC MEANS ONLY. THE REMOTE CONTROL LIGHT OF THE |
| | GARAGE DOOR OPENER DOES NOT MEET THESE REQUIREMENTS. |
| | 5. FBC-RE3901.4.2: A GFI OUTLET IS MISSING ON THE |
| | KITCHEN COUNTER ADJACENT TO REFRIGERATOR. |
| | 6. FBC-RE3901.10: WITHOUT KNOWING THE SCALE OF THE |
| | DRAWINGS IT IS IMPOSSIBLE TO PROPERLY ASCERTAIN |
| | RECEPTACLE PLACEMENT REQUIREMENTS, BUT IF THE CORRIDOR |
| | TO THE BEDROOMS IS 10' OR GREATER, AN OUTLET IS |
| | REQUIRED IN THE HALLWAY. |
| | 7. FBC-RE3903.3: A LIGHTING OUTLET SHALL BE INSTALLED |
| | ON THE EXTERIOR OF THE LAUNDRY ROOM AND THE GARAGE |
| | DOOR. |
| | 8. FBC-R315: YOU SHALL INSTALL CARBON MONOXIDE |
| | DETECTION WITHIN 10 FT. OF THE BEDROOM DOORS. THIS |
| | APPLIES TO THE DEVICE IN THE HALLWAY, IT SHALL BE A |
| | COMBINATION UNIT CAPABLE OF DETECTING BOTH, HIGH LEVELS |
| | OF SMOKE AND CARBON MONOXIDE. |
| | 9. IN THE INTEREST OF LIFE SAFETY, OWNER CONVENIENCE |
| | AND ENERGY CONSERVATION, PLEASE LET ME SUGGEST THAT YOU |
| | INSTALL ADDITIONAL LIGHTING CONTROLS FOR THE DINING |
| | ROOM AND THE EXISTING ENTRY PORCH LEADING INTO THE |
| | GARAGE ENTRANCE. SEE MARK ON PLANS OR CALL ME FOR |
| | FURTHER DETAILS. |
| | 10. FBC-ER404.1 A MINIMUM OF 75% OF THE LAMPS IN |
| | PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE |
| | HIGH-EFFICACY LAMPS OR A MINIMUM OF 75% OF THE |
| | PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN |
| | ONLY HIGH EFFICIENCY LAMPS |
| | 11. YOU SHALL SHOW THE LOCATION OF ALL HVAC EQUIPMENT |
| | AND ALL ASSOCIATED EQUIPMENT ON THE PLANS. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |