| 2016-08-11 13:53:18 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | PROJECT NAME: SACCO RESIDENCE |
| | JOB ADDRESS: 836 ARDMORE RD. |
| | DESCRIPTION: PARTIAL REWIRE OF HOUSE; INSTALL ARC-FAULT |
| | MASTER PERMIT: 16080322 |
| | REVISION: |
| | |
| | BELOW ARE COMMENTS RELATED TO THE FAILED ELECTRICAL |
| | REVIEW: |
| | |
| | 1. FBC-R 107.2.1: THE SCOPE IS TOO VAGUE TO ACCEPT. YOU |
| | HAVE TO BE MORE SPECIFIC WITH THE SCOPE OF WORK. |
| | 2. FBC-B 109.3: YOU NEED TO PROVIDE A COPY OF THE |
| | ACCEPTED CONTRACT. |
| | 3. FBC-R 107.2.1: YOU SHALL INCLUDE ON THE PLANS THE |
| | NAME AND ADDRESS OF THE JOB LOCATION. |
| | 4. FBC-R 3701.2: YOU SHALL PROVIDE A FEEDER SCHEDULE |
| | (RISER DIAGRAM) SHOWING THE LOCATION OF BOTH PANEL AND |
| | THEIR RESPECTIVE DISCONNECTS. |
| | 5. FBC-R 3604: YOU SHALL SUBMIT A SITE DIAGRAM |
| | INDICATING THE LOCATION OF THE METER AND DISCONNECTS ON |
| | THE PREMISES. |
| | 6. ON THE PLANS MARK WHAT IS NEW AND WHAT IS EXISTING |
| | TO REMAIN. |
| | 7. FBC-R 3902.11/.12: ALL NEW WORK SHALL COMPLY WITH |
| | THE GFCI & ARC-FAULT REQUIREMENTS. |
| | 8. FBC-R3706.2: YOU SHALL PROVIDE A PANEL SCHEDULE OR |
| | CIRCUIT DIRECTORY LEGIBLY INDICATING THE SPECIFIC |
| | PURPOSE OF EVERY CIRCUIT. |
| | 9. FBC-R4002.14: ALL NEW RECEPTACLES IN ALL AREAS |
| | SPECIFIED IN 210.52, ALL 125-VOLT, 15 AND 20 AMPERE |
| | RECEPTACLES SHALL BE LISTED TAMPER RESISTANT |
| | RECEPTACLES. |
| | 10. FBC-R 314/315: YOU SHALL COME INTO COMPLIANCE |
| | W/SMOKE DETECTOR REQUIREMENTS AS FOR NEW CONSTRUCTION. |
| | IF THERE ARE ANY FOSSIL FUEL (GAS) BURNING APPLIANCES |
| | ON SITE YOU SHALL ABIDE BY THE CARBON MONOXIDE |
| | REQUIREMENT AS WELL. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |
| | EMAIL: [email protected] |
| | |