| 2016-11-18 15:43:48 | MECHANICAL PROVISOS: | | | 11/18/16 | | | | | | 1) PROVIDE MANUFACTURER'S SPECIFICATIONS FOR THE FABRIC | | | DUCTWORK WITH REVIEW SIGNATURE BY THE ENGINEER OF | | | RECORD, OR REVISE PLANS TO PROVIDE ALTERNATE APPROVED | | | DUCTWORK. | | | | | | 2) RELOCATE THE OUTSIDE AIR INLETS FOR AHU-1 & 2 TO A | | | LOCATION THAT IS A MINIMUM OF 10' FROM STREETS, | | | A;LLEYS, OR PARKLING LOTS- SECTION 401.4 FBC-14 | | | MECHANICAL. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|