| Plan Review Notes For Permit 16080300 |
| Permit Number |
16080300 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-10-28 08:56:55 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #16080300 | | | 10/28/16 | | | | | | 1) THE LETTER FROM ROCAMAR ENGINEERING HAS BEEN | | | FORWARDED TO ROBERT BROWN- BUILDING OFFICIAL FOR | | | REVIEW. FINAL APPROVAL OF THE MECHANICAL PLANS ARE | | | CONTINGENT ON APPROVAL OF THE LETTER REQUEST TO EXCLUDE | | | EXHAUST VENTILATION FOR THE ART CLASSROOMS, AND TO | | | RETAIN THE CURRENT MECHANICAL DESIGN. | | | | | | 2) THE AC CLOSET DOORS SHALL BE NON-COMBUSTIBLE PER | | | SECTION C403.2.7.2 FBC-14 ENERGY CONSERVATION. NOTE 20 | | | ON SHEET A100 IS INDICATING WOOD. | | | | | | 3) PLEASE PROVIDE ON THE PLAN THE FABRIC DUCT | | | MANUFACTURER AND SUBMIT SPECIFICATIONS WITH APPROVAL | | | SIGNATURE BY THE EOR- SECTION 603. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|