| 2016-08-12 10:43:26 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | PROJECT NAME: FUSION HAIR SALON |
| | JOB ADDRESS: 321 S. DIXIE HWY. |
| | DESCRIPTION: INTERIOR IMPROVEMENT ? NEW HAIR SALON |
| | MASTER PERMIT: 16080290 |
| | |
| | BELOW ARE COMMENTS RELATED TO THE FAILED ELECTRICAL |
| | REVIEW: |
| | |
| | 1. NEC 700.12 (F) (4) - EMERGENCY LIGHTING SHALL BE FED |
| | BY LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR MORE |
| | LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY BE ON |
| | OWN CIRCUIT, OTHERWISE THEY SHALL BE ON THE SAME |
| | CIRCUIT AS FOR THE LIGHTING OF THE ROOM THEY OCCUPY. |
| | 2. NEC 600.5 - EACH COMMERCIAL BUILDING AND EACH |
| | COMMERCIAL OCCUPANCY ACCESSIBLE TO PEDESTRIANS SHALL BE |
| | PROVIDED WITH AT LEAST ONE 20 AMP DEDICATED OUTLET IN |
| | AN ACCESSIBLE LOCATION AT EACH ENTRANCE TO EACH TENANT |
| | SPACE FOR SIGN OR OUTLINE LIGHTING. SERVICE HALLWAYS OR |
| | CORRIDORS SHALL NOT BE CONSIDERED ACCESSIBLE TO |
| | PEDESTRIANS. THE SUBMITTED DRAWING DOES NOT INDICATE |
| | THIS ON THE PANEL SCHEDULE OR THE FLOOR PLAN. |
| | 3. NEC 210.62 SHOW WINDOWS. AT LEAST ONE RECEPTACLE |
| | OUTLET SHALL BE INSTALLED WITHIN 18? OF THE TOP OF A |
| | SHOW WINDOW FOR EVERY 12 LINEAR FT. OR MAJOR PORTION |
| | THEREOF AREA MEASURED HORIZONTALLY. THE SUBMITTED |
| | DRAWING DOES NOT INDICATE THIS ON THE PANEL SCHEDULE OR |
| | THE FLOOR PLAN. |
| | 4. NEC 422.31. PERMANENTLY CONNECTED APPLIANCE OF OVER |
| | 300 VA OR 1/8 HP REQUIRES A DISCONNECT WITHIN SIGHT OF |
| | THE APPLIANCE. MARK ON THE PLANS THE DISCONNECT FOR THE |
| | WATER HEATER. |
| | 5. NEC 110.16 ARC-FLASH HAZARD WARNING: ELECTRICAL |
| | EQUIPMENT IN OTHER THAN DWELLING UNITS LIKELY TO |
| | REQUIRE SERVICE WHILE ENERGIZED SHALL BE FIELD MARKED |
| | TO WARN AGAINST POTENTIAL ARC-FAULT HAZARDS. THIS CAN |
| | BE ADDRESSED WITH A BLOCK NOTE ON THE PLANS. |
| | 6. NEC 110.24 THE MAXIMUM AVAILABLE FAULT CURRENT SHALL |
| | BE DURABLY MARKED AND DATED ON ALL NON-DWELLING |
| | ELECTRICAL APPARATUS. THIS CAN BE ADDRESSED WITH A |
| | BLOCK NOTE ON THE PLANS. |
| | 7. NEC 110.26(D) ILLUMINATION. ILLUMINATION SHALL BE |
| | PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE |
| | EQUIPMENT, SWITCHBOARDS, AND PANELBOARDS. THIS LIGHT |
| | SHALL NOT BE CONTROLLED BY AUTOMATIC MEANS ONLY. |
| | 8. FBC-E SECTION C405 REQUIRES MANDATORY LIGHTING |
| | CONTROL. |
| | 9. FBC-EC 405.2.2.2 REQUIRES OCCUPANCY SENSORS IN THE |
| | RESTROOMS, STORAGE CLOSET, PRIVATE OFFICES AND SIMILAR |
| | ROOMS. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |