| Plan Review Notes For Permit 16080277 |
| Permit Number |
16080277 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-08-16 08:16:08 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #16080277 | | | 8/16/16 | | | | | | 1) REFER TO SECTION 107.1 WPB AMENDMENTS TO THE FBC- | | | PLANS SHALL BE SUBMITTED IN TWO OR MORE SETS. ONLY ONE | | | SET OF PLANS WAS SUBMITTED FOR REVIEW. | | | | | | 2) REFER TO SECTION 105.3.1.2 WPB AMENDMENTS TO THE | | | FBC- THE MECHANICAL PLANS SHALL BE DESIGNED BY A FL. | | | LICENSED ENGINEER OR THE THE INSTALLING AC CONTRACTOR. | | | | | | 3) SHEET M-2: INDICATE HOW AIR IS BEING RETURNED FROM | | | OFFICE #5, AND RECEPTION ROOM 100- SECTION 601.5. | | | | | | 4) M-2: THE 24X12 (288 SQ, INCHES) RETURN AIR GRILL IN | | | THE CONFERENCE ROOM IS UNDERSIZED FOR 760 CFMS. | | | TYPICALLY RETURN GRILLS ARE SIZED CFM/2 ( 1 SQ. IN. OF | | | GRILL AREA PER 2CFMS OF AIR). 760 CFMS REQUIRES 380 SQ. | | | IN. OF RETURN. | | | | | | 5) M-2: INDICATE THE SIZE OF THE EXISTING DUCT | | | SUPPLYING OFFICE #5 AND CONFERENCE 101. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|