Plan Review Notes
Plan Review Notes For Permit 16080277
Permit Number 16080277
Review Stop M
Sequence Number 1
Notes
Date Text
2016-08-16 08:16:081ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16080277
 8/16/16
  
 1) REFER TO SECTION 107.1 WPB AMENDMENTS TO THE FBC-
 PLANS SHALL BE SUBMITTED IN TWO OR MORE SETS. ONLY ONE
 SET OF PLANS WAS SUBMITTED FOR REVIEW.
  
 2) REFER TO SECTION 105.3.1.2 WPB AMENDMENTS TO THE
 FBC- THE MECHANICAL PLANS SHALL BE DESIGNED BY A FL.
 LICENSED ENGINEER OR THE THE INSTALLING AC CONTRACTOR.
  
 3) SHEET M-2: INDICATE HOW AIR IS BEING RETURNED FROM
 OFFICE #5, AND RECEPTION ROOM 100- SECTION 601.5.
  
 4) M-2: THE 24X12 (288 SQ, INCHES) RETURN AIR GRILL IN
 THE CONFERENCE ROOM IS UNDERSIZED FOR 760 CFMS.
 TYPICALLY RETURN GRILLS ARE SIZED CFM/2 ( 1 SQ. IN. OF
 GRILL AREA PER 2CFMS OF AIR). 760 CFMS REQUIRES 380 SQ.
 IN. OF RETURN.
  
 5) M-2: INDICATE THE SIZE OF THE EXISTING DUCT
 SUPPLYING OFFICE #5 AND CONFERENCE 101.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  