Plan Review Notes
Plan Review Notes For Permit 16080277
Permit Number 16080277
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-08-10 13:03:311555 PALM BEACH LAKES BOULEVARD - SUITE #1105
 PERMIT #16080277
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PLANS INDICATE AN OCCUPANT LOAD OF 46 PERSONS FOR THE
 SPACE; HOWEVER, THE CONFERENCE ROOM WILL ADD
 APPROXIMATELY 25 PERSONS WHEN USING AN OCCUPANT LOAD
 FACTOR OF 15 SQ.FT. PER PERSON. THIS OCCUPANT LOAD
 ADJUSTMENT WILL REQUIRE THE EXIT ACCESS DOORS (#1 AND
 #5) TO SWING IN THE OPPOSITE DIRECTION. PER NFPA 101
 SECTION 7.2.1.4.2, DOORS ARE REQUIRED TO SWING IN THE
 DIRECTION OF EGRESS TRAVEL FOR AN OCCUPANT LOAD OF 50
 OR GREATER PERSONS.
  
 NO ENGINEERED FIRE ALARM DRAWINGS SUBMITTED. PER FBC
 SECTION 907.1.1 CONSTRUCTION DOCUMENTS - "CONSTRUCTION
 DOCUMENTS FOR FIRE ALARM SYSTEMS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE, THE FLORIDA
 FIRE PREVENTION CODE, AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL."
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE