| Notes |
| Date |
Text |
| 2016-08-10 13:03:31 | 1555 PALM BEACH LAKES BOULEVARD - SUITE #1105 | | | PERMIT #16080277 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PLANS INDICATE AN OCCUPANT LOAD OF 46 PERSONS FOR THE | | | SPACE; HOWEVER, THE CONFERENCE ROOM WILL ADD | | | APPROXIMATELY 25 PERSONS WHEN USING AN OCCUPANT LOAD | | | FACTOR OF 15 SQ.FT. PER PERSON. THIS OCCUPANT LOAD | | | ADJUSTMENT WILL REQUIRE THE EXIT ACCESS DOORS (#1 AND | | | #5) TO SWING IN THE OPPOSITE DIRECTION. PER NFPA 101 | | | SECTION 7.2.1.4.2, DOORS ARE REQUIRED TO SWING IN THE | | | DIRECTION OF EGRESS TRAVEL FOR AN OCCUPANT LOAD OF 50 | | | OR GREATER PERSONS. | | | | | | NO ENGINEERED FIRE ALARM DRAWINGS SUBMITTED. PER FBC | | | SECTION 907.1.1 CONSTRUCTION DOCUMENTS - "CONSTRUCTION | | | DOCUMENTS FOR FIRE ALARM SYSTEMS SHALL BE OF SUFFICIENT | | | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF | | | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL | | | CONFORM TO THE PROVISIONS OF THIS CODE, THE FLORIDA | | | FIRE PREVENTION CODE, AND RELEVANT LAWS, ORDINANCES, | | | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING | | | OFFICIAL." | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | | | | | | | |
|