| 2016-08-15 07:53:32 | 1ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES | | | PERMIT #16080247 | | | 8/15/16 | | | | | | 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE | | | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL | | | ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL. | | | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND | | | PROVIDED CFMS OF OUTDOOR AIR. PLEASE NOTE THAT LOCKER | | | ROOMS REQUIRE EXHAUST AT A RATE OF 0.5 CFM'S PER SQ. | | | FT. AND RECIRCULATION OF AIR IS LIMITED TO 10% OF THE | | | SUPPLY AIR STREAM. | | | | | | 2) PROVIDE A SCOPE OF WORK FOR MECHANICAL ALTERATIONS | | | THAT INDICATES WHICH AREAS OF THE OCCUPANCY ARE BEING | | | CONDITIONED BY THE NEW AC SYSTEMS. | | | | | | 3) SHEET M-1.1: SHOW THE LOCATIONS OF THE EXISTING | | | AHU'S AND SUPPLY, RETURN, AND O/A DUCTWORK. HOW CAN THE | | | O/A BRANCH DUCTS TO THE NEW UNITS BE EXISTING? PLEASE | | | INDICATE THE SIZES OF THE EXISTING AND NEW O/A DUCTS. | | | | | | 4) M-1.1: PROVIDE COMPLETE SUPPLY AND RETURN DUCTWORK | | | PLANS FOR THE NEW AHU'S. HOW IS AIR BEING RETURNED TO | | | THE UNITS FROM ALL THE ROOMS AND SPACES? | | | | | | 5) M-1.1: A NEW MECHANICAL CLOSET IS BEING CREATED FOR | | | AHU-1. PLEASE NOTE THAT ALL MATERIALS IN THE CLOSET | | | INCLUDING THE NEW DOOR SHALL BE NON-COMBUSTIBLE OR | | | PLENUM-RATED- SEE SECTION C403.2.7.2 FBC-14 ENERGY | | | CONSERVATION. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|