| 2016-08-12 07:44:18 | |
| | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16080184 |
| | ADD: 3700 S. DIXIE HWY. SUITES 5-6 |
| | CONT: ANDERSON CONSTRUCTION |
| | TEL: 5561-255-5464 |
| | E-MAIL: INFO@ADERSON CONSTRUCTIONFL.COM |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. AUGUST 12/ 2016 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE NOTE THERE IS NO HEADERSTRIP ON THE PLANS |
| | PROVIDING AN ADDRESS WHERE THE WORK IS GOING TO OCCURR. |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION OF THE |
| | PROPOSED PROJECT. |
| | |
| | 2) 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.3.5. MINIMUM PLAN REVIEW CRITERIA |
| | FOR COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | OCCUPANCY TYPE: |
| | MINIMUM BUILDING TYPE |
| | FIRE SPRINKLERED OR NOT |
| | SQ. FT. OF BUILDING. |
| | SQ. FT. OF TENANT SPACE |
| | OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| | OCCUPANCY LOAD |
| | GROSS |
| | NET |
| | MEANS OF EGRESS |
| | EXIT ACCESS |
| | EXIT |
| | EMERGENCY LIGHTING AND EXIT SIGNS |
| | |
| | 3)THE CONTRACTOR OF RECORD (QAULIFIER) THAT CREATE THE |
| | PLAN FOR THE PROPOSED WORK WILL NEED TO PRINT THEIR |
| | NAME, SIGN THEIR NAME & PRINT THEIR LICENSE NUMBER ON |
| | THE PLANS THEY HAVE CREATED. 2014 FLORIDA BUILDING CODE |
| | W 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.1. |
| | 107.3.4.3 CERTIFICATIONS BY CONTRACTORS AUTHORIZED |
| | UNDER THE PROVISIONS OF SECTION 489.115 FLORIDA |
| | STATUTES, SHALL BE CONSIDERED EQUIVALENT TO SEALED |
| | PLANS AND SPECIFICATIONS BY A PERSON LICENSED UNDER |
| | CHAPTER 471, FLORIDA STATUTES, OR CHAPTER 481 FLORIDA |
| | STATUTES. |
| | |
| | 4) PLANS NEED TO BE BOUND TOGETHER INTO ONE SET OF |
| | DOCUMENTS BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. |
| | 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS |
| | SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE. THE |
| | BUILDING OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL |
| | POLICY, OTHER STANDARDS FOR PLANS AND SPECIFICATIONS, |
| | IN |
| | ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION |
| | PROGRAM. |
| | |
| | 5) PLEASE INDICATE WHICH WAY THE CEILING/ RAFTER/ OR |
| | ROOF JOIST ARE POSITIONED. THE TENANT SEPARATION WALL |
| | MAY ALSO BE A BEARING WALL, REQUIRING A PROPERLY SIZED |
| | HEADER, JACK STUDS AND FULL LENGTH BEARING STUDS. THIS |
| | SAME WALL IF IT IS A BEARING WALL WOULD ALSO BE |
| | CONSIDERED PART OF THE MWFRS (MAIN WIND FORCE RESISTING |
| | SYSTEM) IN THAT CASE THE CONTRACTOR CAN NOT DESIGN |
| | LOADS TO RESIST WIND LOADS UNLESS CERTIFIED THEOUGH A |
| | STATE APPROVED COURSE, THIS COURSE AND CERTIFICATE WAS |
| | FOR |
| | WIND LOADS ON ONE & TWO FAMILY RESIDENCE. |
| | |
| | 107.3.4.3 CERTIFICATIONS BY CONTRACTORS AUTHORIZED |
| | UNDER THE PROVISIONS OF SECTION489.115 FLORIDA |
| | STATUTES, SHALL BE CONSIDERED EQUIVALENT TO SEALED |
| | PLANS AND SPECIFICATIONS BY A PERSON LICENSED UNDER |
| | CHAPTER 471, FLORIDA STATUTES, OR CHAPTER 481 FLORIDA |
| | STATUTES, BY LOCAL ENFORCEMENT AGENCIES FOR PLANS |
| | REVIEW FOR PERMITTING PURPOSES RELATING TO COMPLIANCE |
| | WITH THE WIND-RESISTANCE PROVISIONS OF THE CODE OR |
| | ALTERNATE METHODOLOGIES ENFORCEMENT AGENCIES MAY RELY |
| | UPON SUCH CERTIFICATION BY CONTRACTORS THAT THE PLANS |
| | AND SPECIFICATIONS SUBMITTED CONFORM TO THE |
| | REQUIREMENTS OF THE CODE FOR WIND RESISTANCE. UPON GOOD |
| | CAUSE SHOWN, LOCAL GOVERNMENT CODE ENFORCEMENT AGENCIES |
| | MAY ACCEPT OR REJECT PLANS SEALED BY PERSONS LICENSED |
| | UNDER CHAPTERS 471,481 OR 489, FLORIDA STATUTES. |
| | |
| | 6) THE PLANS INDICATE THE CONTRACT VALUE OF THE PROJECT |
| | IS $ 4,200.00 DOLLARS. 20% OF THE CONTRACT VALUE OR |
| | $840.00 DOLLARS IS TO BE SPENT ON ACCESSIBLE UPGRADES. |
| | PLEASE SEE THE ORDER THE FUNDS ARE TO BE SPENT. THE |
| | CONTRACTOR IS TO PROVIDE AN ITEMIZED LIST INTHE ORDER |
| | LISTED BELOW OF WHAT ACCESSIBLE ELEMENTS ARE GOING TO |
| | BE UPGRADED TO CODE COMPLIANCE. |
| | 2014 FBC-ACCESSIBILITY CODE. 202.4.1 DISPROPORTIONATE |
| | COST. ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF |
| | TRAVEL TO THE ALTERED AREA WILL BE DEEMED |
| | DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE |
| | COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE |
| | PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS |
| | EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF |
| | TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING |
| | AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE |
| | ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING |
| | RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS, |
| | ENLARGING TOILET STALLS, INSULATING PIPES, OR |
| | INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS |
| | ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH |
| | AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT, |
| | INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT |
| | TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING |
| | AN INACCESSIBLE DRINKING FOUNTAIN. |
| | |
| | 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |