2016-08-08 17:44:00REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 1) CLARIFY PANEL SCHEDULE "A" CIRCUIT # 13,15
 REFLECTING A 30 AMP DOUBLE POLE BREAKER FOR LIVING &
 BEDOOM ?
  
 2) ADD A GFCI 20 AMP RECEPTACLE FOR NEW VANITY IN
 MASTER BATHROOM, THE OUTLET SHALL BE WITHIN 3' OF SINK
 EDGE. NEC 210.8(A)(1) & 210.11(C)(3).
  
 3) SMOKE ALARMS REQUIRED PER RESIDENTIAL CODE 314 &
 315. IF EXISTING MAKE A NOTE.
  
 4) ALL NEWLY INSTALLED RECEPTACLES SHALL BE
 TAMPER-RESISTANT PER NEC 406.12. A NOTE WILL SUFFICE.