| Plan Review Notes For Permit 16080121 |
| Permit Number |
16080121 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-09-09 15:21:59 | PLAN DENIED | | | 1) THERE IS NO ADDRESS ON PLAN SECTION 107.2.1 FBC 2014 | | | 2) PROVIDE ENGINEERING ON PLAN FOR CONDENSER TIE DOWN | | | PER SECTION M1305.1.4.1 GROUND CLEARANCE AND | | | M1401.4 EXTERIOR INSTALLATION 2014 RESIDENTIAL CODE | | | 3) REFER TO SECTION R403.2.4 AIR HANDLING UNITS | | | 2014 FLORIDA ENERGY CODE. | | | 4) REFER TO SECTION M1305.1.3 APPLIANCES IN ATTIC | | | 2014 RESIDENTIAL CODE | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|