| 2016-08-08 18:39:03 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | PROJECT NAME: 1700 PBL, LLC |
| | JOB ADDRESS: 1700 PALM BEACH LAKES BLVD. |
| | DESCRIPTION: LIKE FOR LIKE SWAP IF INTERIOR 300KW |
| | GENERATOR |
| | MASTER PERMIT:16080092 |
| | REVISION: |
| | |
| | 1. SECTION 107.2.1 OF THE WPB CITY AMENDMENTS REQUIRE |
| | THAT THE CONSTRUCTION DOCUMENTS BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE PROPOSED WORK AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO CODE REQUIREMENTS. (CLEARLY DEFINE YOUR |
| | SCOPE OF WORK ON THE PLANS). SUCH DRAWINGS SHALL |
| | INDICATE THE APPLICABLE DESIGN CODE, AND FURTHERMORE, |
| | THE DRAWINGS SHALL BEAR THE NAME AND SIGNATURE OF THE |
| | PERSON RESPONSIBLE FOR THE DESIGN. (YOUR NAME AND |
| | SIGNATURE SHALL APPEAR ON ALL DOCUMENTS). |
| | 2. YOU SHALL PROVIDE MANUFACTURER?S SPECS FOR THE |
| | PROPOSED GENERATOR. LIKE FOR LIKE MAY REFER TO HAVING |
| | REMOVED A 300 KW UNIT TO BE REPLACE W/ONE OF EQUAL |
| | SIZE, BUT NOT NECESSARILY THE SAME. |
| | 3. PER THE SCOPE AS DEFINED ON THE PERMIT APPLICATION, |
| | THE EXTENT OF THE WORK PERFORMED DOES NOT MATCH THAT |
| | REFLECTED ON THE PLANS. PLEASE LIMIT THE PLANS TO THE |
| | SCOPE OF WORK. |
| | 4. A 300 KW UNIT MAY HAVE BEEN SUFFICIENT AT THE TIME |
| | OF INITIAL INSTALLATION THAT DOES NOT MEAN THAT IT WILL |
| | BE SUFFICIENT FOR TODAY?S LOAD. IN LIEU OF LOAD CALCS, |
| | PROVIDE 1 YEAR MAXIMUM DEMAND DATA, OR OTHER LOAD |
| | CALCULATION METHOD AS DESCRIBED IN NEC 220.87. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |