Plan Review Notes
Plan Review Notes For Permit 16080090
Permit Number 16080090
Review Stop E
Sequence Number 1
Notes
Date Text
2016-08-23 08:06:14RESPONDED TO CALL/ NO ANSWER LEFT MESSAGE W/VOICE MAIL.
 PER A TELEPHONE CONVERSATION W/MR. BENNETT, ALL
 ELECTRICAL WORK RELATED TO THE BATHROOM REMODEL IS
 BEING DONE UNDER PERMIT 16061642.
2016-08-04 12:07:35ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 PROJECT NAME:
 JOB ADDRESS: 234 30TH ST.
 DESCRIPTION: MASTER BATH REMODEL
 MASTER PERMIT:16080090
 REVISION:
  
 1. SECTION 107.2.1 OF THE WPB CITY AMENDMENTS REQUIRE
 THAT THE CONSTRUCTION DOCUMENTS BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE PROPOSED WORK AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO CODE REQUIREMENTS. (CLEARLY DEFINE YOUR
 SCOPE OF WORK ON THE PLANS). SUCH DRAWINGS SHALL
 INDICATE THE APPLICABLE DESIGN CODE, AND FURTHERMORE,
 THE DRAWINGS SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. (YOUR NAME AND
 SIGNATURE SHALL APPEAR ON ALL DOCUMENTS).
 2. FBC-RE3901.6/NEC 210.52(D) BATHROOMS. IN DWELLING
 UNITS, AT LEAST ONE GFI PROTECTED RECEPTACLE OUTLET
 SHALL BE INSTALLED IN BATHROOMS WITHIN 3 FT. OF THE
 OUTSIDE EDGE OF EACH BASIN.
 3. FBC-ER3903.2/NEC 210.70(A)(1): AT LEAST ONE WALL
 SWITCH CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED IN
 EVERY HABITABLE ROOM AND BATHROOM.
 4. FBC-R4002.14/NEC 406.12 TAMPER-RESISTANT RECEPTACLES
 IN DWELLING UNITS. IN ALL AREAS SPECIFIED IN 210.52,
 ALL 125-VOLT, 15 AND 20 AMPERE RECEPTACLES SHALL BE
 LISTED TAMPER RESISTANT RECEPTACLES.
 5. FBC-R314 REQUIRES THAT YOU COME INTO COMPLIANCE WITH
 THE SMOKE DETECTOR REQUIREMENTS AS IF FOR NEW
 CONSTRUCTION.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  