| Plan Review Notes For Permit 16080089 |
| Permit Number |
16080089 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-08-03 18:59:46 | CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA | | | BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION | | | | | | 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1 | | | INFORMATION ON CONSTRUCTION DOCUMENTS | | | | | | (1) PROVIDE LOCATION OF WHERE MINI-SPLIT AHU IS | | | LOCATED. | | | | | | FLORIDA ENERGY CODE FBC 2014 | | | | | | R101.4.5 CHANGE IN SPACE CONDITIONING. | | | ANY NONCONDITIONED SPACE THAT IS ALTERED TO BECOME | | | CONDITIONED SPACE SHALL BE REQUIRED TO BE BROUGHT INTO | | | FULL COMPLIANCE WITH THIS CODE. | | | | | | R405.4 DOCUMENTATION. | | | DOCUMENTATION OF THE SOFTWARE USED FOR THE PERFORMANCE | | | DESIGN AND THE PARAMETERS FOR THE BUILDING SHALL BE IN | | | ACCORDANCE WITH SECTIONS R405.4.1 THROUGH R405.4.3. | | | | | | (2) PROVIDE HEAT LOAD CALCULATIONS MANUAL J | | | | | | (3) PROVIDE ENERGY CALCULATIONS FORM R405-2014 | | | | | | (4) PROVIDE EXHAUST FOR BATHROOM | | | | | | JORGE VALIDO | | | WPB MECHANICAL INSPECTOR/PLANS EXAMINER | | | [email protected] | | | 561-805-6716 | | | |
|