| Notes |
| Date |
Text |
| 2016-08-04 10:41:00 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | - PROVIDE A SITE SPECIFIC PLAN SHOWING A/C DISCONNECT | | | WITHIN SIGHT FOR BOTH INDOOR AND OUTDOOR UNITS PER NEC | | | 440 | | | | | | - NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A 125 VOLT, | | | SINGLE-PHASE, 15 OR 20-AMPERE-RATED RECEPTACLE OUTLET | | | SHALL BE INSTALLED AT AN ACCESSIBLE LOCATION FOR THE | | | SERVICING OF HVAC EQUIPMENT. THE RECEPTACLE SHALL BE | | | LOCATED WITHIN 25 FT. OF THE EQUIPMENT. |
|