2016-08-03 08:21:10INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. MULTIPLE DISCREPANCIES ON REVISION SUBMITTED. MUST
 MATCH FIELD INSTALLATION. SHOW RISER AS BUILT IN THE
 FIELD, PER DAN KEMPA (FIELD INSPECTOR). REFLECT A 400A
 MAIN ON RISER. PROVIDE REVISED AIC CALCULATION AND
 AVAILABLE FAULT PER FPL. FBC 107.3.5
 2. THE PLANS SUBMITTED HAVE NON APPLICABLE NOTES FOR
 WHAT IS NOW BEING SHOWN. 400A MAIN NOT SHOWN. 6 MAINS
 STILL REFLECTED ON NOTES. 600A SERVICE NOTES STILL ON
 DOCUMENTS. FBC 107.3.5
 3. SHOW A COMPLETE STANDARD CALCULATION OR OPTIONAL PER
 NEC 220. LOADS TO BE VERIFIED FOR 400A SERVICE.
 ORIGINAL SUBMITTED DRAWINGS BY AOR DIFFER FROM EOR
 SUBMITTING NOW. PLEASE CLARIFY.
 4. COMMENTS TO FOLLOW.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II