| Plan Review Notes For Permit 16080068 |
| Permit Number |
16080068 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-08-03 08:21:10 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 | | | COMMENTS: | | | | | | 1. MULTIPLE DISCREPANCIES ON REVISION SUBMITTED. MUST | | | MATCH FIELD INSTALLATION. SHOW RISER AS BUILT IN THE | | | FIELD, PER DAN KEMPA (FIELD INSPECTOR). REFLECT A 400A | | | MAIN ON RISER. PROVIDE REVISED AIC CALCULATION AND | | | AVAILABLE FAULT PER FPL. FBC 107.3.5 | | | 2. THE PLANS SUBMITTED HAVE NON APPLICABLE NOTES FOR | | | WHAT IS NOW BEING SHOWN. 400A MAIN NOT SHOWN. 6 MAINS | | | STILL REFLECTED ON NOTES. 600A SERVICE NOTES STILL ON | | | DOCUMENTS. FBC 107.3.5 | | | 3. SHOW A COMPLETE STANDARD CALCULATION OR OPTIONAL PER | | | NEC 220. LOADS TO BE VERIFIED FOR 400A SERVICE. | | | ORIGINAL SUBMITTED DRAWINGS BY AOR DIFFER FROM EOR | | | SUBMITTING NOW. PLEASE CLARIFY. | | | 4. COMMENTS TO FOLLOW. | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | |
|