| 2016-08-31 11:31:25 | 2ND REVIEW FBC-2014 MECHANICAL |
| | PERMIT #16080066 |
| | 8/31/16 |
| | |
| | PLEASE REVIEW THE 1ST REVIEW COMMENTS PRINTED BELOW |
| | REGARDING THE AC PLAN. THE COMMENTS REMAIN APPLICABLE |
| | TO THE RESUBMITTED PLANS. IN ADDITION PLEASE NOTE THE |
| | FOLLOWING: THE INSTALLING AC CONTRACTOR MAY DRAW, SIGN, |
| | AND SUBMIT AC PLANS, BUT MUST ALSO SUBMIT A SUB-PERMIT |
| | APPLICATION. THE INSTALL AC CONTRACTOR'S PLANS MUST |
| | SHOW ONLY DETAILS FOR THE AC SYSTEM, AND NOT CONTAIN |
| | |
| | ANY ARCHITECTURAL DETAILS AND SCHEDULES PREPARED BY THE |
| | ARCHITECT OF RECORD. THE WPB BUILDING DEPT. IS |
| | REQUIRING A SIGNED AND SEALED LETTER FROM THE ARCHITECT |
| | OF RECORD HARVARD JOLLY STATING THAT THEY ARE NOT |
| | PROVIDING THE DESIGN OF THE MEP SYSTEMS, HOWEVER THEY |
| | MAY ALLOW THE CONTRACTOR TO USE THEIR FLOOR PLAN OR |
| | REFLECTIVE CEILING DRAWING AS THE BASIS FOR THE AC |
| | SYSTEM PLANS. |
| | |
| | 1) TWO A1.1 PLANS SHEETS HAVE BEEN SUBMITTED. ONE SHEET |
| | IS SIGNED AND SEALED BY THE ARCHITECT OF RECORD- RENE |
| | TERCILLA AIA. THE OTHER A1.1 PLAN SHEET IS NOT SIGNED |
| | AND SEALED AND HAS A HANDWRITTEN AC PLAN AND NOTES |
| | WRITTEN OVER THE CEILING DETAIL. THIS PLAN WILL NOT BE |
| | REVIEWED AND MUST BE DISCARDED PER FLORIDA STATUTE |
| | 481.221(2), FLORIDA ADMINISTRATIVE CODE 61G1-16.003. |
| | |
| | 2) REFER TO SECTION 107.1 WPB AMENDMENTS TO THE FBC AND |
| | RESUBMIT MECHANICAL PLANS THAT INCLUDE: A SCOPE OF WORK |
| | OUTLINE FOR THE PROJECT, AC EQUIPMENT SCHEDULE, DUCT |
| | LAYOUT PLAN, AIR DISTRIBUTION AND DEVICE SCHEDULES, |
| | COOLING AND HEATING CALCULATIONS, CONDENSATE DISPOSAL, |
| | O/A CALCULATIONS AND CONTROLS, ENERGY COMPLIANCE, SMOKE |
| | AND FIRE PROTECTION TRANSFER OPENING PROTECTIONS, |
| | FIRESTOPPING DETAILS, AND DUCT HANGING AND SUPPORT |
| | DETAILS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |