| 2016-09-27 19:36:39 | ELECTRICAL REVIEW APPROVED. ALL PREVIOUSLY MENTIONED |
| | DEFICIENCIES HAVE BEEN SATISFACTORILY ADDRESSED. |
| 2016-09-23 10:12:31 | 3RD ELECTRICAL REVIEW: |
| | REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 & |
| | NFPA 70 2011 (NEC) |
| | |
| | PROJECT NAME: DOCK/PIER & SEAWALL |
| | JOB ADDRESS: 3200 WASHINGTON RD. |
| | DESCRIPTION: REPAIR 102 FT. OF SEAWALL; REPLACE DOCK |
| | W/PIER, ACCESS PIER AND PLATFORM. INSTALL A 16K & A 10K |
| | LB. FOUR POLE BOAT LIFT. |
| | MASTER PERMIT: 16080055 |
| | |
| | 0. NOW THAT AN ELECTRICAL SHEET HAS BEEN PROVIDED, |
| | BELOW ARE THE DEFICIENCIES NOTED AT THE TIME OF THE |
| | ELECTRICAL PLAN REVIEW. |
| | SECTION 107.2.1.4 OF THE WPB CITY AMENDMENTS TO THE |
| | FBC-B REQUIRES THAT BUILDING PLANS BE DRAWN TO A |
| | MINIMUM 1/8? SCALE. THE PLANS SUBMITTED ARE WAY TOO |
| | SMALL TO BE LEGIBLE. |
| | 1. PROVIDE PROOF OF THE REQUIRED LONGSHORE & HARBOR |
| | WORKERS COMPENSATION INSURANCE. |
| | YOU WERE PREVIOUSLY ASKED TO PROVIDE PROOF OF LONGSHORE |
| | & HARBOR WORKERS COMP AS REQUIRED BY TITLE 33 CHAP 18 |
| | OF THE DEPT. OF LABOR. |
| | 2. SECTION 107.2.1 OF THE WPB CITY AMENDMENTS REQUIRE |
| | THAT THE CONSTRUCTION DOCUMENTS BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE PROPOSED WORK AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO CODE REQUIREMENTS. (CLEARLY DEFINE YOUR |
| | SCOPE OF WORK ON THE PLANS). SUCH DRAWINGS SHALL |
| | INDICATE THE APPLICABLE DESIGN CODE, AND FURTHERMORE, |
| | THE DRAWINGS SHALL BEAR THE NAME AND SIGNATURE OF THE |
| | PERSON RESPONSIBLE FOR THE DESIGN. (YOUR NAME AND |
| | SIGNATURE SHALL APPEAR ON ALL DOCUMENTS). |
| | THE DOCUMENTS ARE NOT YET SIGNED AS REQUIRED. |
| | 3. YOU SHALL INCLUDE ON THE SITE DRAWING THE LOCATION |
| | OF THE OVERCURRENT PROTECTION AND OR DISCONNECTS FOR |
| | THE PIER. |
| | THERE SHALL BE A READILY ACCESSIBLE DISCONNECT ON LAND |
| | TO DISCONNECT ALL POWER TO THE PIER. |
| | 4. YOU WILL NEED TO PROVIDE A WIRING DIAGRAM AND LOAD |
| | CALCS FOR THE PROPOSED INSTALLATION INCLUDING THE |
| | INDIVIDUAL MOTOR LOADS. |
| | YOU MENTIONED THE CONCURRENT LOADS BETWEEN THE SHORE |
| | POWER AND LIFT, BUT LOAD CALCS SHALL BE PROVIDED. YOU |
| | MAY CONSIDER IN THE CALCS EACH LIFT AS A UNIT. |
| | 5. IF THE POWER WILL BE PROVIDED UNDER A SEPARATE |
| | PERMIT, YOU NEED TO PROVIDE THAT NUMBER AND INCLUDE ON |
| | THE DRAWING THE AVAILABLE POWER. |
| | SATISFIED: POWER TO PIER PROVIDED UNDER PERMIT |
| | 16071076. |
| | 6. FBC?R4002.9 NEC 406.9(B) RECEPTACLES IN WET |
| | LOCATIONS: 15 AND 20 AMPERE, 125 AND 250 VOLT |
| | RECEPTACLES INSTALLED IN A WET LOCATION SHALL HAVE AN |
| | ENCLOSURE THAT IS WEATHERPROOF WHETHER OR NOT THE |
| | ATTACHMENT PLUG CAP IS INSERTED. ALL 15 AND 20 AMPERE, |
| | 125 AND 250 VOLT NONLOCKING RECEPTACLES SHALL BE LISTED |
| | WEATHER?RESISTANT TYPE WR. THIS APPLIES TO THE OUTLETS |
| | IN THE PEDESTAL AS WELL. |
| | SATISFIED: THE OUTLETS INSTALLED ON THE PEDESTALS |
| | COMPLY WITH THIS REQUIREMENT, BUT YOU MAY HAVE TO |
| | REPLACE THE OUTLETS WITH ONES THAT ARE LISTED WEATHER |
| | RESISTANT AS REQUIRED BY CODE. |
| | 7. NEC 555.19(B)(2): ALL RECEPTACLES OTHER THAN THOSE |
| | DESIGNATED FOR SHORE POWER SHALL BE MARKED TO INDICATE |
| | THAT THEY ARE NOT TO BE USED FOR SHORE POWER TO BOATS. |
| | THIS CAN BE ADDRESSED WITH A BLOCK NOTE TO BE VERIFIED |
| | IN THE FIELD. |
| | |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |
| | EMAIL: [email protected] |
| | |