| Plan Review Notes For Permit 16080054 |
| Permit Number |
16080054 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-08-03 08:28:57 | 1ST REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING | | | PERMIT #16080054 | | | 8/3/16 | | | | | | 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE | | | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL | | | ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL. | | | | | | 2) PROVIDE OUTDOOR AIR SHUTOFF DAMPER CONTROLS FOR EACH | | | AC SYSTEM IN COMPLIANCE WITH SECTION C403.2.4.4 FBC-14 | | | ENERGY CONSERVATION . | | | | | | 3) PROVIDE A TERMINAL BOX SCHEDULE. | | | | | | 4) PROVIDE AN AIR DEVICE SCHEDULE. | | | | | | 4) SHEET M02.102: PROVIDE DUCT SMOKE DETECTORS IN THE | | | RETURN AIR SYSTEMS OF RTU-2 AND RTU-4. SHOW A SYMBOL ON | | | THE PLAN. | | | | | | 5) M02.102: INCLUDE THE FLEX DUCTS IN THE SCHEDULE. | | | | | | 6) M02.102, NOTE #5: THE REQUIRED EXHAUST CFMS IN THE | | | TOILET ROOMS BY THE WEST STAIRS SHALL BE 70 CFMS OR 50 | | | CFMS IF RUNNING CONTINUOUSLY WHILE OCCUPIED- TABLE | | | 403.3. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|