2016-08-03 08:28:571ST REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING
 PERMIT #16080054
 8/3/16
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
  
 2) PROVIDE OUTDOOR AIR SHUTOFF DAMPER CONTROLS FOR EACH
 AC SYSTEM IN COMPLIANCE WITH SECTION C403.2.4.4 FBC-14
 ENERGY CONSERVATION .
  
 3) PROVIDE A TERMINAL BOX SCHEDULE.
  
 4) PROVIDE AN AIR DEVICE SCHEDULE.
  
 4) SHEET M02.102: PROVIDE DUCT SMOKE DETECTORS IN THE
 RETURN AIR SYSTEMS OF RTU-2 AND RTU-4. SHOW A SYMBOL ON
 THE PLAN.
  
 5) M02.102: INCLUDE THE FLEX DUCTS IN THE SCHEDULE.
  
 6) M02.102, NOTE #5: THE REQUIRED EXHAUST CFMS IN THE
 TOILET ROOMS BY THE WEST STAIRS SHALL BE 70 CFMS OR 50
 CFMS IF RUNNING CONTINUOUSLY WHILE OCCUPIED- TABLE
 403.3.
  