| 2016-08-03 14:32:13 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | PROJECT NAME: INTERIOR BUILDING RENOVATIONS - COMMON |
| | AREAS |
| | JOB ADDRESS: 324 DATURA ST. |
| | DESCRIPTION: INTERIOR BUILDING RENOVATIONS - COMMON |
| | AREAS |
| | MASTER PERMIT:16080044 |
| | |
| | |
| | 1. THERE SEEMS TO BE A MIX UP WITH THIS SUBMITTAL. THE |
| | PERMIT APPLICATION DOES NOT CLEARLY IDENTIFY THE AREA |
| | OF WORK. THERE ARE TWO SEPARATE PLAN SETS ONE OF WHICH |
| | IS THE ARCHITECTURAL AND THE OTHER THE MEP AND THEY DO |
| | NOT MATCH. THE ELECTRICAL SET DOES NOT INDICATE THE |
| | AREA DRAWN WHILE THE ARCHITECTURAL SET ADDRESSES |
| | SEVERAL FLOORS. PLEASE PROVIDE ONE COMPLETE SET AND |
| | HAVE IT ALL MATCH. |
| | 2. WITHOUT A DEFINED AREA OF WORK AND KNOWLEDGE OF WHAT |
| | ARE THE EXITS IT IS IMPRACTICABLE TO DETERMINE PROPER |
| | EXIT LIGHT PLACEMENT. CORRECT THE PLANS ACCORDINGLY. |
| | 3. YOU SHALL INCLUDE A LIGHT DENSITY ALLOWANCE CHART AS |
| | INDICATED IN THE FBC-E 405.5.2 |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |
| | EMAIL: [email protected] |
| | |