| 2016-08-02 15:19:06 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | FBC 2010 & NFPA 70 2008 (NEC) |
| | |
| | PROJECT: |
| | JOB ADDRESS: 1220 ORTEGA RD. |
| | DESCRIPTION: MECHANICAL & ELECTRICAL CHANGES |
| | MAST. PERMIT: 15060911 |
| | REVISION: 16080035 |
| | |
| | THE LACK OF A NARRATIVE PROMPTED ME TO REVIEW THE |
| | COMPLETE SUBMITTAL TO FIND THAT THERE WERE ELECTRICAL |
| | CHANGES BEYOND THE CORRECTIONS REQUIRED FROM PREVIOUS |
| | REVIEW. BELOW ARE THE CORRECTIONS REQUIRED FOR A |
| | SUCCESSFUL ELECTRICAL REVIEW. |
| | 1. YOU WERE PREVIOUSLY INFORMED OF THE SIGN OUTLET |
| | REQUIREMENT OF NEC 600.5 WHICH WAS NOT COMPLIED WITH ON |
| | THE RESUBMITTAL. |
| | 2. THERE IS AN EXIT OUT OF THE MAIN WAREHOUSE AREA |
| | LEADING INTO AN EXISTING OFFICE. THERE IS NO INDICATION |
| | OF EXISTING EXIT OR EMERGENCY LIGHTING IN THAT AREA. |
| | PLEASE INDICATE IF THERE IS EMERGENCY AND EXIT LIGHTING |
| | IN THAT SPACE AND IF THERE IS NOT, PLEASE CORRECT TO |
| | INCLUDE. SEE FBC 2010 SECTIONS 1006 & 1011. (W/O A |
| | COMPASS POINT ON THE PLANS IT IS DIFFICULT TO IDENTIFY |
| | THE LOCATION. IN THE FUTURE PLEASE INCLUDE A COMPASS |
| | POINT ON ALL PLANS). |
| | 3. IDENTIFY ALL PANELS ON THE FLOORPLAN TO MATCH THE |
| | RISER DIAGRAM. THERE ARE THREE(3) PANELS REFLECTED ON |
| | THE FLOOR PLAN, 2 EXISTING AND 1 NEW. THE RISER DIAGRAM |
| | SHOWS 5 PANELS, FOUR (4) EXISTING AND A NEW. WHICH IS |
| | CORRECT AND HAVE THEM MATCH? |
| | 4. PROVIDE LOAD CALCS FOR THE SERVICE NOT JUST THE NEW |
| | PANEL. |
| | 5. CORRECT THE CIRCUIT DIRECTORY OF PANEL A TO MATCH |
| | CIRCUIT DESIGNATION ON THE FLOOR PLANS FOR THE NEW |
| | EVAP. UNITS. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |
| | EMAIL: [email protected] |
| | |