| Plan Review Notes For Permit 16080027 |
| Permit Number |
16080027 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-08-05 09:35:17 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #16080027 | | | 8/5/16 | | | | | | 1) PROVIDE A NARRATIVE FROM THE DESIGN PROFESSIONAL | | | LISTING ALL CHANGES TO THE APPROVED PLANS. | | | | | | 2) THE TWO- 24X24 TRANSFER GRILLS ARE UNDERSIZED FOR | | | 2600 CFMS OF SUPPLY AIR- SEE SECTION 601.5(2) AND | | | ENLARGED THE GRILLS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|