| Plan Review Notes For Permit 16080025 |
| Permit Number |
16080025 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-12-15 17:16:59 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #16080025 | | | 12/15/16 | | | | | | 1) THERE APPEARS TO BE INADEQUATE MAKEUP AIR FOR THE | | | KITCHEN EXHAUST HOODS AND INADEQUATE COMBUSTION AIR FOR | | | THE APPLIANCES. THE AIR BALANCE SCHEDULE INDICATES 1550 | | | CFMS OF O/A FOR THE 2000 CFM KITCHEN HOOD EXHAUST. | | | PLEASE REFER TO SECTION 508.1 WHICH REQUIRES THE AMOUNT | | | OF MAKEUP AIR TO BE APPROXIMATELY EQUAL TO THE AMOUNT | | | OF EXHAUST AIR. | | | | | | SECTION 304.9.3 FBC-14 FUEL GAS REQUIRES THE MECHANICAL | | | VENTILATION SYSTEM TO PROVIDE THE SPECIFIED 201 CFMS OF | | | COMBUSTION AIR IN ADDITION TO THE REQUIRED VENTILATION | | | AIR. THE PROPOSED DESIGN INDICATES ALL AIR VENTILATION | | | AIR IS BEING USED AS MAKEUP AIR FORE THE HOODS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|