| 2016-08-25 14:21:45 | 1) SHT.A-0.1 - THE ACCESSIBILITY DETAILS SHOWN ON THE |
| | DRAWING IS FROM AN OUTDATED EDITION OF THE |
| | ACCESSIBILITY CODE. THE CODE IN EFFECT IS THE 2014 |
| | FBC-ACCESSIBILITY. |
| | 2) THE "SOPE OF WORK " BOX REFERS TO THIS LOCATION AS |
| | TO BEING IN MIAMI BEACH. REVISE THE NOTE. |
| | 3) SHT.A-0.1 - THE GRAB BARS SHALL BE MEASURED TO THE |
| | TOP OF THE GRIPPING SURFACE NOT TO THE CENTERLINE. 2014 |
| | FAC SEC. 609.4. |
| | 4) SHT.A-3.0 - NOTES THE OVERFLOW SCUPPER AS 12 INCHES |
| | BY 8 INCHES BUT DETAIL # 7 ON SHT. A-3.1 NOTES THE |
| | OVERFLOW SCUPPERR AS 8 INCHES BY 16 INCHES. CLARIFY. |
| | 5) SHOW THE CLEAR FLOOR SPACE FOR THE WATER CLOSET AND |
| | THE LAVATORY IN DETAIL #1 ON SHEET A-6.0.THE DIMENSION |
| | LINES ARE SO LIGHT THEY ARE ILLEGIBLE. COMPLY WITH FAC |
| | SECS.604.3, 606.2. |
| | 6) SHT. A-6.0 - THE DOORS ON THE TOILET ROOMS APPEAR TO |
| | SWING INTO THE CLEAR FLOOR SPACE FOR THE LAVATORIES. |
| | COMPLY WITH FAC SEC.603.2.3. |
| | 7) SHT. A-6.0 - CLEARLY SHOW THE DIMENSION LINES ON THE |
| | ENLARGED FLOOR PLAN AND ALSO ON THE ELEVATION DETAILS. |
| | FBC !07.2.1. |
| | 8) SHT. A-6.0 - THE LOCATION OF THE TOILET DISPENSER |
| | SHALL COMPLY WITH 2014 FAC SEC.604.7. SEE NOTE #7 IN |
| | GENERAL NOTES. |
| | 9) THE DISTANCE OF THE GRAB BARS (MIN. & MAX. |
| | DIMENSIONS) FROM ADJACENT WALLS SHALL COMPLY WITH 2014 |
| | FAC SECS.604.5. |
| | 10) SHT. P-1 & P-5 - THE SAMPLING PORT DESCIBED AND |
| | SHOWN ON THE SHEETS IS NOT ACCEPTABLE. THE WPB |
| | UTILITIES REQUIRES EITHER A FACTORY MANUFACTURED |
| | SAMPLING PORT OR 6 INCH TWO-WAY CLEANOUT. |
| | 11) A BACKFLOW PREVENTER IS REQUIRED ON THE WATER |
| | FILTER SYSTEM PER 2014 FPC SEC.608.3. |
| | 12) A SEPARATE PERMIT WILL BE REQUIRED FOR THE BACKFLOW |
| | PREVENTION DEVICE AT THE METER FOR THE DOMESTIC WATER |
| | SERVICE AND THE IRRIGATION SYSTEM. |
| | 13) SHT. P-3 NOTES THE GREASY WASTE LINE TO THE |
| | SANITARY SYSTEM.CLARIFY. |
| | 14) THE ICE BIN SHALL NOT DRAIN TO THE SANITARY. 2014 |
| | FPC SEC.1003.2. |
| | 15) SHT. P-1 SHOWS A FLOOR SINK AND A FLOOR DRAIN IN |
| | THE KITCCHEN AREA BUT IT IS NOT SHOWN ON THE RISER ON |
| | P-3. CLARIFY. |
| | 16) ALL HOSE BIBBS SHALL HAVE A SHUTOFF VALVE PER 2014 |
| | FPC SEC. 606.2. |
| | 17) INDICATE THE SIZE OF THE EXISTING GREASE TRAP AND |
| | SUBMIT SIZING CALCULATIONS TO ENSURE ADEQUATE CAPACITY. |
| | 2014 FPC SEC. 1003.2. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |