Plan Review Notes
Plan Review Notes For Permit 16080025
Permit Number 16080025
Review Stop P
Sequence Number 1
Notes
Date Text
2016-08-25 14:21:451) SHT.A-0.1 - THE ACCESSIBILITY DETAILS SHOWN ON THE
 DRAWING IS FROM AN OUTDATED EDITION OF THE
 ACCESSIBILITY CODE. THE CODE IN EFFECT IS THE 2014
 FBC-ACCESSIBILITY.
 2) THE "SOPE OF WORK " BOX REFERS TO THIS LOCATION AS
 TO BEING IN MIAMI BEACH. REVISE THE NOTE.
 3) SHT.A-0.1 - THE GRAB BARS SHALL BE MEASURED TO THE
 TOP OF THE GRIPPING SURFACE NOT TO THE CENTERLINE. 2014
 FAC SEC. 609.4.
 4) SHT.A-3.0 - NOTES THE OVERFLOW SCUPPER AS 12 INCHES
 BY 8 INCHES BUT DETAIL # 7 ON SHT. A-3.1 NOTES THE
 OVERFLOW SCUPPERR AS 8 INCHES BY 16 INCHES. CLARIFY.
 5) SHOW THE CLEAR FLOOR SPACE FOR THE WATER CLOSET AND
 THE LAVATORY IN DETAIL #1 ON SHEET A-6.0.THE DIMENSION
 LINES ARE SO LIGHT THEY ARE ILLEGIBLE. COMPLY WITH FAC
 SECS.604.3, 606.2.
 6) SHT. A-6.0 - THE DOORS ON THE TOILET ROOMS APPEAR TO
 SWING INTO THE CLEAR FLOOR SPACE FOR THE LAVATORIES.
 COMPLY WITH FAC SEC.603.2.3.
 7) SHT. A-6.0 - CLEARLY SHOW THE DIMENSION LINES ON THE
 ENLARGED FLOOR PLAN AND ALSO ON THE ELEVATION DETAILS.
 FBC !07.2.1.
 8) SHT. A-6.0 - THE LOCATION OF THE TOILET DISPENSER
 SHALL COMPLY WITH 2014 FAC SEC.604.7. SEE NOTE #7 IN
 GENERAL NOTES.
 9) THE DISTANCE OF THE GRAB BARS (MIN. & MAX.
 DIMENSIONS) FROM ADJACENT WALLS SHALL COMPLY WITH 2014
 FAC SECS.604.5.
 10) SHT. P-1 & P-5 - THE SAMPLING PORT DESCIBED AND
 SHOWN ON THE SHEETS IS NOT ACCEPTABLE. THE WPB
 UTILITIES REQUIRES EITHER A FACTORY MANUFACTURED
 SAMPLING PORT OR 6 INCH TWO-WAY CLEANOUT.
 11) A BACKFLOW PREVENTER IS REQUIRED ON THE WATER
 FILTER SYSTEM PER 2014 FPC SEC.608.3.
 12) A SEPARATE PERMIT WILL BE REQUIRED FOR THE BACKFLOW
 PREVENTION DEVICE AT THE METER FOR THE DOMESTIC WATER
 SERVICE AND THE IRRIGATION SYSTEM.
 13) SHT. P-3 NOTES THE GREASY WASTE LINE TO THE
 SANITARY SYSTEM.CLARIFY.
 14) THE ICE BIN SHALL NOT DRAIN TO THE SANITARY. 2014
 FPC SEC.1003.2.
 15) SHT. P-1 SHOWS A FLOOR SINK AND A FLOOR DRAIN IN
 THE KITCCHEN AREA BUT IT IS NOT SHOWN ON THE RISER ON
 P-3. CLARIFY.
 16) ALL HOSE BIBBS SHALL HAVE A SHUTOFF VALVE PER 2014
 FPC SEC. 606.2.
 17) INDICATE THE SIZE OF THE EXISTING GREASE TRAP AND
 SUBMIT SIZING CALCULATIONS TO ENSURE ADEQUATE CAPACITY.
 2014 FPC SEC. 1003.2.
  