| 2016-08-09 15:41:44 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #16080025 | | | 8/9/16 | | | | | | 1) ADVISORY: SEPARATE PERMITS AND PLANS ARE REQUIRED | | | FOR KITCHEN HOODS, FIRE SUPPRESSION, AND WALK-IN | | | COOLERS AND FREEZERS. PLEASE PLACE THESE NOTES IN BOLD | | | LETTERS ON THE PLANS. | | | | | | 2) THE SEQUENCE OF OPERATION ON SHEET H-5 SEEM TO | | | INDICATE THERE IS A SUPPLY FAN FOR THE KITCHEN EXHAUST | | | HOODS, HOWEVER THER IS NO SUPPLY FAN SHOWN ON THE | | | PLANS. CLARIFY HOW MAKE-UP AIR WILL BE SUPPLIED AND | | | ACTIVATED FOR THE HOODS, AND HOW COMPLIANCE WITH | | | SECTION 508.1.1 WILL BE MET FOR MAKEUP AIR TEMPERATURE. | | | | | | 3) REFER TO SECTION 304 FBC-14 FUEL GAS AND INDICATE | | | HOW COMBUSTION AIR WILL BE PROVIDED FOR THE GAS-FIRED | | | COOKING APPLIANCES AND SHOW CALCULATIONS. PLEASE SEE | | | SECTION 304.9.3 FOR MECHANICAL COMBUSTION AIR | | | COMPLIANCES. | | | | | | 4) M-2 & H-6: THE RTU'S AND FANS MUST BE ANCHORED TO | | | RESIST THE WIND LOADS AS OUTLINED IN SECTION 1609 | | | FBC-14 BUILDING. PLEASE PROVIDE THE CURRENT WIND LOAD | | | DESIGN CRITERIA ON THE PLANS: BASIC WIND SPEED, WIND | | | SPEED CONVERSION, IMPORTANCE FACTOR, EXPOSURE CATEGORY, | | | AND HEIGHT AND EXPOSURE ADJUISTMENT COEFFICIENT. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|