Plan Review Notes
Plan Review Notes For Permit 16080025
Permit Number 16080025
Review Stop G
Sequence Number 1
Notes
Date Text
2016-08-25 14:35:091) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL GAS
 EQUIPMENT/APPLIANCES. EQUIPMENT/APPLIANCES SHALL BE
 LISTED AND LABELED PER 2014 FBC-FUEL GAS SEC. 301.3.
 2) SUBMIT COMBUSTION AIR CALCULATIONS FOR ALL GAS
 APPLIANCES IN ACCORDANCE WITH FGC SEC.304. SEE FGC SEC.
 304.9.3 FOR MECHANICAL COMBUSTION AIR COMPLIANCE.
 3) SUBMIT VENTING DETAILS FOR THE GAS WATER HEATERS.FGC
 SEC. 503.
 4) SHT. P-3 - SIZE ALL SECTIONS OF THE GAS RISER
 DIAGRAM. FBC SEC. 107.2.1, FGC SECS.401.8, 402.1,
 402.3.
 5) SHT. P-3 - TABLE 402.4 (2) IS REFERENCED ON THE PLAN
 IN THE GAS SYSTEM DESIGN WITH A PRESSURE DROP OF 10.5
 INCHES OF WATER COLUMN. THE PRESSURE DROP FOR THIS
 TABLE IS 0.5 INCHES. CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW