| 2016-08-03 11:26:08 | JOB PERMIT NUMBER: 16080025 |
| | JOB ADDRESS: 1210 N DIXIE HWY |
| | WEST PALM BEACH FLORIDA |
| | DATE: AUGUST 3, 2016 |
| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | |
| | 1) WHEN USING THE TOTAL BUILDING METHOD PER TABLE FBC-E |
| | SECTION C405.5.2 THE ALLOWED W/SQFT IS 1.4 WATTS. |
| | PLEASE CORRECT CALCULATION ON LIGHT DENSITY CHART. |
| | 2) NEC 700.12 (F) (4) EMERGENCY/EXIT LIGHTING SHALL BE |
| | FED BY LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR |
| | MORE LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY |
| | BE ON OWN CIRCUIT. |
| | 3) ADD EMERGENCY LIGHTING BY THE SITTING AREA. THE |
| | MEANS OF EGRESS ILLUMINATION LEVEL SHALL NOT BE LESS |
| | THAN 1' CANDLE AT THE WALKING SURFACE. FBC-1006.2 |
| | 4) PROVIDE A LUMINAIRE SUPPORT DETAIL TO REFLECT HOW |
| | THE LIGHTING IS ATTACHED TO THE SUSPENDED CEILING. |
| | MECHANICAL FASTENING IS PERMITTED, HOWEVER VERIFY ANSI |
| | STANDARDS FOR CEILING GRID LOADS. NEC 410.36(B) |
| | 5) NEC 600.5 REQUIRED BRANCH CIRCUIT. EACH COMMERCIAL |
| | BUILDING AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO |
| | PEDESTRIANS SHALL BE PROVIDED WITH AT LEAST ONE 20 AMP |
| | DEDICATED OUTLET IN AN ACCESSIBLE LOCATION AT EACH |
| | ENTRANCE TO EACH TENANT SPACE FOR SIGN OR OUTLINE |
| | LIGHTING. SERVICE HALLWAYS OR CORRIDORS SHALL NOT BE |
| | CONSIDERED ACCESSIBLE TO PEDESTRIANS |
| | 6) NEC 210.62 SHOW WINDOWS. AT LEAST ONE RECEPTACLE |
| | OUTLET SHALL BE INSTALLED WITHIN 18? OF THE TOP OF A |
| | SHOW WINDOW FOR EVERY 12 LINEAR FT OR MAJOR PORTION |
| | THEREOF AREA MEASURED HORIZONTALLY. |
| | 7) AMBIENT TEMPERATURE ADJUSTMENT FACTORS MUST BE TAKEN |
| | INTO CONSIDERATION FOR CONDUCTORS AND CONDUITS ON |
| | ROOFTOPS, IF CONDUCTOR LENGTH IS OVER 10' OR 10 % |
| | EXPOSED TO SUNLIGHT THE HIGHER AMPACITY MUST BE USED. |
| | NEC 310.15(C) |
| | 8) LOW VOLTAGE , FIRE ALARM , AND EXTERIOR SITE |
| | LIGHTING SHALL BE UNDER A SEPARATE PERMIT. A BLOCK NOTE |
| | WILL SUFFICE. |
| | |
| | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED DEFICIENCIES. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. |
| | THE NARRATIVE SHOULD INCLUDE THE PLAN REVIEWER'S |
| | COMMENTS AND YOUR RESPONSE OR ACTION TO SAME. |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO THE |
| | SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON'T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | FBC 2014 5TH ED. NEC 2011 |