Plan Review Notes
Plan Review Notes For Permit 16080025
Permit Number 16080025
Review Stop B
Sequence Number 1
Notes
Date Text
2016-09-01 10:36:48BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16080025
 ADD: 1210 N. DIXIE HWY.
 CONT: BURGER GULF
 TEL: 850-629-9805
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. SEPT. 01/2016
 ACTION: DENIED
  
 1) PLEASE NOTE THIS PERMIT DESCRIPTION FOR THE SCOPE OF
 WORK IS FOR A NEW BURGER KING RESTAURANT. TO DATE THERE
 HAS BEEN NO PERMIT APPLIED FOR, TO DEMOLISH THE CURRENT
 STRUCTURE. WE WILL NEED A DEMO PERMIT APPLIED FOR
 BEFORE THE ISSUANCE OF THIS PERMIT. THE OTHER ISSUE IS
 IN ORDER NOT TO HAVE TO PAT IMPACT FEES ON THE NEW
 BUILDING OR ONLY A PORTION OF THE BUILDING. A
 CERTIFICATE OF COMPLETION FOR THE REMOVAL OF THE
 EXISTING BUILDING WOULD BE REQUIRED TO GET THE CREDIT
 FROM THE PALM BEACH COUNTY IMPACT FEE OFFICE. FOR
 FURTHER INFORMATION PLEASE CALL (561) 233-5025.
  
 2) SHEET S-0 FOUNDATION NOTE 1 & 2 BOTH INDICATE
 LETTERS REQUIRED BY THE CITY OF MIAMI-DADE. PLEASE
 DELETE THESE NOTES SINCE THEY DO NOT HAVE ANY
 SIGNIFICANCE ON THE PROJECT. THIS PROJECT IS NOT
 LOCATED IN THE HIGH VELOCITY HURRICANE ZONE. 107.2.1.3
 DISCREPANCY IN THE PLANS.
  
 3) SHEET S-0 FOUNDATION NOTE E INDICATES THE FOUNDATION
 MAY BE LOWERED 6 INCHES LOWER INTO THE LIMESTONE BASED
 ON THE BEST AVAILABLE SOIL BEARING LOADS. THIS AGAIN
 SOUNDS LIKE THE TYPE OF SOILS FOUND IN THE MIAMI-DADE
 AREA WHERE THE LIMESTONE BEDROCK IS JUST BELOW GRADE.
 THERE IS GOING TO BE A BUILDING DEMOLISHED FROM THIS
 SITE WILL THERE BE SOILS BORING TO BE TAKEN OR IS THERE
 GOING TO BE A MINIMUM DENSITY REQUIRED FOR A MINIMUM
 BEARING VALUE REQUIRED FOR THE STEM WALL FOUNDATION?
 NOTE I SPEAKS ABOUT THE DENSITY REQUIRED FOR THE SLAB
 ON GRADE. FBC-B 1803.5.2 QUESTIONABLE SOIL.
  
 4) SHEET S-0 NOTE H INDICATES THE USE OF CONCRETE
 FOUNDATIONS ARE PERMITTED TO BE CAST AGAINST THE EARTH
 WHERE IN THE OPINION OF THE BUILDING OFFICIAL, SOIL
 CONDITIONS DO NOT REQUIRE FORMWORK. PLEASE NOTE THE
 SOILS IN THIS AREA DOES REQUIRE THE FOUNDATION TO BE
 FORMED. 2014 FBC-B 1808.8.5.
  
 5) SHEET S-0 HEADING 7 DESIGN LOADS (B) GIVE THE WIND
 DESIGN CRITERIA 170 VULT EXP. C ASCE 7-10. PLEASE
 REVIEW SHEET S-7 WINDOW & DOOR REQUIREMENTS INDICATES
 THE REQUIREMENTS WERE DESIGNED TO THE 2014 FBC-B & ASCE
 7-05. PLEASE NOTE THE 2014 FBC-B 1609.1.1 AND CHAPTER
 35 REFERENCE THE ASCE 7-10 NOT THE ASCE 7-05.
  
 6) SHEET S-7 THE WINDOW AND DOOR CHARTS APPEAR TO BE
 LOW BY APPROXIMATELY 4 PSF FROM THE TABLES FOUND IN THE
 ASCE 7-10 FIGURE 30.5-1.
  
 7) SHEET S-7 DOES NOT PROVIDE NOR ANY OTHER STRUCTURAL
 SHEET PROVIDE THE ROOF PRESSURES FOR ROOF ZONES 1,2 AND
 3. 2014 FBC-B 1603.1.4 WIND DESIGN DATA. 5. DESIGN WIND
 PRESSURES TO BE USED FOR EXTERIOR COMPONENT AND
 CLADDING MATERIALS NOT SPECIFICALLY DESIGNED BY THE
 REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR THE
 DESIGN OF THE STRUCTURE, PSF (KN/ M2).
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
 PLEASE CONVERT THE PRESSURES TO VASD SINCE THE PRODUCT
 APPROVALS ARE IN VASD. 1609.3.1 WIND SPEED CONVERSION
 VULT TO VASD.
  
 8) COMPONENTS & CLADDING. 2014 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS,
 EXHAUST FANS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
 NOTE EITHER THE CONTRACTOR OR DESIGNER OF RECORD PREFER
 TO SUBMIT THE PRODUCT APPROVALS AFTER PERMIT ISSUANCE
 PLEASE SEE:
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
  
 9) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 10) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR
 BOTH INSULATION & THE BASE SHEET AS CALCULATED IN
 COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117.
 CALCULATION PREPARED, SIGNED AND SEALED BY A FLORIDA
 REGISTERED PROFESSIONAL ENGINEER OR REGISTERED
 ARCHITECT.
  
 11) SHEET A-3 AND M2 SHOW SOME GENERIC RTU CURB
 DETAILS. PLEASE PROVIDE CURB DETAILS FOR THE RTU UNITS,
 EXHAUST FAN AND CURBS , CONNECTIONS OF THE CURB TO THE
 ROOF FRAMING(MWFRS) AND FROM THE CURB TO THE UNIT. FOR
 ALL ROOF TOP EQUIPMENT, CURBS OR A/C STANDS, DETAILED
 ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL AS FROM
 THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS?
  
 12) SHEET A-1.2 THE SEATING LAYOUT PLAN, PLEASE SHOW
 COMPLIANCE ACCESSIBILITY CODE 226.1 WHERE DINING
 SURFACES ARE PROVIDED FOR THE CONSUMPTION OF FOOD OR
 DRINK, AT LEAST 5 PERCENT OF THE SEATING SPACES AND
 STANDING SPACES AT THE DINING SURFACES SHALL COMPLY
 WITH 902. CHART SHOW 72 SEATS X 0,05= 4 PLEASE PROVIDE
 WHERE THE 4 ACCESSIBLE SEATS ARE LOCATED.
  
 12A) ACCESS. CODE 902.2 CLEAR FLOOR OR GROUND SPACE. A
 CLEAR FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR A
 FORWARD APPROACH SHALL BE PROVIDED. KNEE AND TOE
 CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
  
 12B) ACCESS. CODE 902.3 HEIGHT. THE TOPS OF DINING
 SURFACES AND WORK SURFACES SHALL BE 28 INCHES (710 MM)
 MINIMUM AND 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 12C) ACCESS. CODE 226.2 DISPERSION. DINING SURFACES AND
 WORK SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE
 DISPERSED THROUGHOUT THE SPACE OR FACILITY CONTAINING
 DINING SURFACES AND WORK SURFACES. SHEET A-1.2 SHOWS
 WHAT APPEARS TO BE ELECTRIC PLUGS AT TABLES AND CHAIRS
 PLEASE SHOW A PORTION OF THESE AT ACCESSIBLE LOCATIONS
 FOR WHEEL CHAIR USERS.
  
 12D) SELF-SERVE COUNTERS SHOW COMPLIANCE WITH: ACCESS.
 CODE 227.3 COUNTERS. WHERE PROVIDED, AT LEAST ONE OF
 EACH TYPE OF SALES COUNTER AND SERVICE COUNTER SHALL
 COMPLY WITH 904.4. WHERE COUNTERS ARE DISPERSED
 THROUGHOUT THE BUILDING OR FACILITY, COUNTERS COMPLYING
 WITH 904.4 ALSO SHALL BE DISPERSED.
  
 13) SHEET A-0.1 & A-0.2 BOTH SHEETS INDICATE THE
 ACCESSIBLE ELEMENTS DEPICTED ARE UNDER THE FEDERAL ADA.
 PLEASE REVISE THE PLANS AND DETAILS TO THE 2014
 FBC-ACCESSIBILITY CODE.
  
 14) SHEET A-0.2 THE HANDRAILS FOR THE WATER CLOSET SHOW
 THE MEASUREMENTS TAKEN FROM THE CENTER LINE OF THE
 HORIZONTAL GRAB BAR. PLEASE NOTE SECTION 609.4 THE
 DIMENSIONS ARE TAKEN FROM FINISH FLOOR TO THE TOP OF
 THE GRASPING SURFACE.
  
 15A) THE SITE PLAN SP-1.0 AND LANDSCAPE PLANS ARE UNDER
 SEPARATE PERMITS. PLEASE SUBMIT THESE PLANS FOR
 REFERENCE ONLY TO BE REVIEWED UNDER A SEPARATE PERMIT.
 105.1 PERMITS REQUIRED.
  
 15B) OTHER PERMITS THAT ARE NOT COVERED UNDER THE
 BUILDING PERMIT ARE IRRIGATION, SIGN, AWNINGS, FIRE
 SPRINKLER, FIRE ALARM, HOODS, ANSIL SYSTEMS, WALK IN
 FREEZERS & COOLERS & GREASE TRAPS, ETC. 105.1 PERMITS
 REQUIRED.
  
 16) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 TO WHOM IT MAY CONCERN:
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  