Plan Review Notes
Plan Review Notes For Permit 16071249
Permit Number 16071249
Review Stop P
Sequence Number 3
Notes
Date Text
2017-03-09 16:41:093RD REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. KITCHEN SINK NOT SHOWN ON RISER DIAGRAM PLEASE
 CLARIFY. WPB AMEND TO FBC 107.2.1
  
 2. THE WASHING MACHINE AND KITCHEN SINK SHALL CONNECT
 TO BUILDING DRAIN DOWN STREAM OF THE BATHROOM GROUP.
 PER FBC RES SECTION P3108 WET VENTING
  
 P3108.1 HORIZONTAL WET VENT PERMITTED.
 ANY COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS
 LOCATED ON THE SAME FLOOR LEVEL SHALL BE PERMITTED TO
 BE VENTED BY A HORIZONTAL WET VENT. THE WET VENT SHALL
 BE CONSIDERED THE VENT FOR THE FIXTURES AND SHALL
 EXTEND FROM THE CONNECTION OF THE DRY VENT ALONG THE
 DIRECTION OF THE FLOW IN THE DRAIN PIPE TO THE MOST
 DOWNSTREAM FIXTURE DRAIN CONNECTION. EACH FIXTURE DRAIN
 SHALL CONNECT HORIZONTALLY TO THE HORIZONTAL BRANCH
 BEING WET VENTED OR SHALL HAVE A DRY VENT. EACH
 WET-VENTED FIXTURE DRAIN SHALL CONNECT INDEPENDENTLY TO
 THE HORIZONTAL WET VENT. ONLY THE FIXTURES WITHIN THE
 BATHROOM GROUPS SHALL CONNECT TO THE WET-VENTED
 HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE HORIZONTAL WET VENT.
  
 3. MUST COMPLY WITH ZONING COMMENTS. PER WPB AMEND TO
 FBC 107.2.1
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  