| 2017-03-28 15:07:17 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 3RD REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY MECHANICAL |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) FBC 107.2.1 PROVIDE THE MODEL NUMBERS AND |
| | SPECIFICATIONS OF THE HEATING AND COOLING EQUIPMENT IN |
| | AN EQUIPMENT SCHEDULE ON THE MECHANICAL PLAN THAT |
| | CORRESPONDS WITH THE EQUIPMENT SIZING CALCULATIONS. THE |
| | INFORMATION ON THE PLANS DOES NOT MATCH THE EQUIPMENT |
| | SIZING CALCULATIONS. THE EQUIPMENT SCHEDULE ON THE |
| | PLANS DOES NOT SPECIFY HEATING. FBCR-M1401.3 |
| | |
| | 2) PROVIDE TWO COPIES OF THE ANCHORING DETAILS FOR THE |
| | OUTSIDE CONDENSING UNIT. FBCR - M1307.2 THE FASTENER |
| | INFORMATION ON THE PLANS IS NOT CLEAR AND THE ANGLE |
| | BRACKET IS NOT DEFINED. YOU MAY WANT TO REVISED THE |
| | MINIMUM THICKNESS OF THE CONCRETE EQUIPMENT PAD. |
| | |
| | 3) SHOW THE BATHROOM VENTILATION AND CLOTHES DRYER |
| | EXHAUST ON THE PLANS. FBC 107.3.5.1.4 MECHANICAL |
| | MINIMUM PLAN REVIEW CRITERIA |
| | |
| | 4) SHOW THE LOCATION OF THE AIR HANDLERS AND THEIR |
| | DISCONNECTS ON THE PLANS. FBC 107.2.1 |
| | |
| | 5) SHOW COMPLIANCE WITH FBCR-M1602.4 FOR BALANCED |
| | RETURN AIR. SPECIFY THE SIZE OF THE TRANSFER GRILL ON |
| | THE PLANS. |
| | |
| | 6) THE ENERGY CALCULATIONS APPEAR TO HAVE A FEW ERRORS. |
| | THE ROOF IS NOT METAL. THERE IS NO KITCHEN SPECIFIED IN |
| | THE ENERGY CALCULATIONS, HOWEVER, THERE IS A KITCHEN |
| | SHOWN ON THE PLANS. PLEASE REVISE THE PLANS OR THE |
| | ENERGY FORMS AS APPROPRIATE. |
| | |
| | 7) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A |
| | RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| | COMMENTS HAS BEEN ADDRESSED. |