Plan Review Notes
Plan Review Notes For Permit 16071249
Permit Number 16071249
Review Stop M
Sequence Number 3
Notes
Date Text
2017-03-28 15:07:17PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.2.1 PROVIDE THE MODEL NUMBERS AND
 SPECIFICATIONS OF THE HEATING AND COOLING EQUIPMENT IN
 AN EQUIPMENT SCHEDULE ON THE MECHANICAL PLAN THAT
 CORRESPONDS WITH THE EQUIPMENT SIZING CALCULATIONS. THE
 INFORMATION ON THE PLANS DOES NOT MATCH THE EQUIPMENT
 SIZING CALCULATIONS. THE EQUIPMENT SCHEDULE ON THE
 PLANS DOES NOT SPECIFY HEATING. FBCR-M1401.3
  
 2) PROVIDE TWO COPIES OF THE ANCHORING DETAILS FOR THE
 OUTSIDE CONDENSING UNIT. FBCR - M1307.2 THE FASTENER
 INFORMATION ON THE PLANS IS NOT CLEAR AND THE ANGLE
 BRACKET IS NOT DEFINED. YOU MAY WANT TO REVISED THE
 MINIMUM THICKNESS OF THE CONCRETE EQUIPMENT PAD.
  
 3) SHOW THE BATHROOM VENTILATION AND CLOTHES DRYER
 EXHAUST ON THE PLANS. FBC 107.3.5.1.4 MECHANICAL
 MINIMUM PLAN REVIEW CRITERIA
  
 4) SHOW THE LOCATION OF THE AIR HANDLERS AND THEIR
 DISCONNECTS ON THE PLANS. FBC 107.2.1
  
 5) SHOW COMPLIANCE WITH FBCR-M1602.4 FOR BALANCED
 RETURN AIR. SPECIFY THE SIZE OF THE TRANSFER GRILL ON
 THE PLANS.
  
 6) THE ENERGY CALCULATIONS APPEAR TO HAVE A FEW ERRORS.
 THE ROOF IS NOT METAL. THERE IS NO KITCHEN SPECIFIED IN
 THE ENERGY CALCULATIONS, HOWEVER, THERE IS A KITCHEN
 SHOWN ON THE PLANS. PLEASE REVISE THE PLANS OR THE
 ENERGY FORMS AS APPROPRIATE.
  
 7) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.