| Plan Review Notes For Permit 16071249 |
| Permit Number |
16071249 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-10-12 08:52:20 | 2ND REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: 2ND REQUEST | | | | | | 1. TOILET NOT SHOWN ON RISER DIAGRAM IT SHALL CONNECT | | | UP STREAM OF THE KITCHEN AND WASHING MACHINE DRAIN. PER | | | FBC PL 912.1 | | | | | | 2.SHOW LOCATION OF NEW AND EXISTING PIPING ON FLOOR | | | PLAN .PER WPB AMEND.TO FBC107.2.1 | | | | | | 3. STUDER VENTS SHOULD BE SHOWN ON TOP OF THE VENT | | | STACKS. PER WPB AMEND.TO FBC107.2.1 | | | | | | 4. SHOW DIMENSIONS FO THE SHOWER AND TOILET SPACE ALONG | | | WITH TOTAL DIMENSIONS OF BATHROOM. PER WPB AMEND.TO | | | FBC107.2.1 | | | | | | 5. ALL PLUMBING DONE WITHOUT A PERMIT SHALL BE EXPOSED | | | AND TESTED FOR INSPECTIONS. PER WPB AMEND.TO FBC | | | 110.3(C)1,2,3 | | | | | | | | | DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND | | | THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON | | | RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS. | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | | | | | FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME. | | | I CAN BE REACHED AT 561-805-6611 OR [email protected] |
|