Plan Review Notes
Plan Review Notes For Permit 16071249
Permit Number 16071249
Review Stop E
Sequence Number 2
Notes
Date Text
2016-09-15 10:17:082ND ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 &
 NFPA 70 2011 (NEC)
  
 PROJECT NAME:
 JOB ADDRESS: 410 31ST STREET
 DESCRIPTION: PERMIT FOR AFTER THE FACT CARPORT
 ENCLOSURE
 MASTER PERMIT: 16071249
  
 BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS.
 ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF
 SUBMITTED CORRECTIONS.
  
 1. THE DECLARED VALUATION WAS CORRECTED TO MATCH GC
 LETTER?S ESTIMATE. VALUE WAS CHANGED FROM $2400.00 TO
 $5000.00.
 2. RECEPTACLE SPACING AS SHOWN ON DRAWINGS DOES NOT
 MEET ELECTRICAL CODE MINIMUMS. IT IS NOT MY INTENT TO
 DESIGN THE JOB FOR YOU BUT I HAVE TAKEN THE LIBERTY TO
 MARK PAGE 2 OF 1 OF THE SETS SUBMITTED WITH THE
 REQUIRED OUTLETS IN ADDITION TO THIS ALREADY MARKED.
 FEEL FREE TO STOP IN TO CHECK OUT A SET OF DRAWINGS AND
 MAKE SURE YOU CHOSE THE ONE MARKED IN GREEN.
 3. AS INDICATED ABOVE, I HAVE MARKED THE MISSING
 LIGHTING OUTLET BY THE FRENCH DOORS.
 A) ALL RECESSED LUMINARIES SHALL BE LISTED THERMALLY
 PROTECTED.
 4. NEC 210.63 REQUIRES THAT THERE BE A GFCI PROTECTED
 OUTLET WITHIN 25? OF THE A/C CONDENSING UNIT. I HAVE
 MARKED THAT AS WELL. THIS DEVICE HAS TO BE IN ADDITION
 TO WEATHER PROOF, BE LIST WEATHER RESISTANT.
 5. THE WATER HEATER WHERE SHOWN ON DRAWINGS IS IN
 VIOLATION OF NEC 110.26 REQUIREMENTS FOR CLEAR WORKING
 CLEARANCES.
 6. SHOW ON THE PLAN THE LOCATION OF THE NEW SUB PANEL.
 7. PROVIDE AN ELECTRICAL RISER DIAGRAM INCLUDING
 CONDUCTOR TYPES AND SITE SPECIFIC LOAD CALCS.
 8. PROVIDE SPEC SHEET FOR HVAC EQUIPMENT TO CONFIRM OCP
 & CONDUCTOR REQUIREMENTS. FURTHERMORE, FBC-R303.9
 REQUIRES THAT YOU PROVIDE HEAT TO THE HABITABLE AREAS.
 9. PROVIDE A RISER DIAGRAM W/LOAD CALCS.
  
 KEEP IN MIND THAT THE INSPECTOR MAY REQUIRE THAT YOU
 OPEN WALLS FOR INSPECTION OF WIRING AND OUTLET BOX
 OPENINGS AND ATTACHMENT ETC.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  