| 2016-09-15 10:17:08 | 2ND ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 & |
| | NFPA 70 2011 (NEC) |
| | |
| | PROJECT NAME: |
| | JOB ADDRESS: 410 31ST STREET |
| | DESCRIPTION: PERMIT FOR AFTER THE FACT CARPORT |
| | ENCLOSURE |
| | MASTER PERMIT: 16071249 |
| | |
| | BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS. |
| | ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF |
| | SUBMITTED CORRECTIONS. |
| | |
| | 1. THE DECLARED VALUATION WAS CORRECTED TO MATCH GC |
| | LETTER?S ESTIMATE. VALUE WAS CHANGED FROM $2400.00 TO |
| | $5000.00. |
| | 2. RECEPTACLE SPACING AS SHOWN ON DRAWINGS DOES NOT |
| | MEET ELECTRICAL CODE MINIMUMS. IT IS NOT MY INTENT TO |
| | DESIGN THE JOB FOR YOU BUT I HAVE TAKEN THE LIBERTY TO |
| | MARK PAGE 2 OF 1 OF THE SETS SUBMITTED WITH THE |
| | REQUIRED OUTLETS IN ADDITION TO THIS ALREADY MARKED. |
| | FEEL FREE TO STOP IN TO CHECK OUT A SET OF DRAWINGS AND |
| | MAKE SURE YOU CHOSE THE ONE MARKED IN GREEN. |
| | 3. AS INDICATED ABOVE, I HAVE MARKED THE MISSING |
| | LIGHTING OUTLET BY THE FRENCH DOORS. |
| | A) ALL RECESSED LUMINARIES SHALL BE LISTED THERMALLY |
| | PROTECTED. |
| | 4. NEC 210.63 REQUIRES THAT THERE BE A GFCI PROTECTED |
| | OUTLET WITHIN 25? OF THE A/C CONDENSING UNIT. I HAVE |
| | MARKED THAT AS WELL. THIS DEVICE HAS TO BE IN ADDITION |
| | TO WEATHER PROOF, BE LIST WEATHER RESISTANT. |
| | 5. THE WATER HEATER WHERE SHOWN ON DRAWINGS IS IN |
| | VIOLATION OF NEC 110.26 REQUIREMENTS FOR CLEAR WORKING |
| | CLEARANCES. |
| | 6. SHOW ON THE PLAN THE LOCATION OF THE NEW SUB PANEL. |
| | 7. PROVIDE AN ELECTRICAL RISER DIAGRAM INCLUDING |
| | CONDUCTOR TYPES AND SITE SPECIFIC LOAD CALCS. |
| | 8. PROVIDE SPEC SHEET FOR HVAC EQUIPMENT TO CONFIRM OCP |
| | & CONDUCTOR REQUIREMENTS. FURTHERMORE, FBC-R303.9 |
| | REQUIRES THAT YOU PROVIDE HEAT TO THE HABITABLE AREAS. |
| | 9. PROVIDE A RISER DIAGRAM W/LOAD CALCS. |
| | |
| | KEEP IN MIND THAT THE INSPECTOR MAY REQUIRE THAT YOU |
| | OPEN WALLS FOR INSPECTION OF WIRING AND OUTLET BOX |
| | OPENINGS AND ATTACHMENT ETC. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |