Plan Review Notes
Plan Review Notes For Permit 16071249
Permit Number 16071249
Review Stop P
Sequence Number 1
Notes
Date Text
2016-08-24 10:15:421ST REVIEW
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
  
 1. TOILET NOT SHOWN ON RISER DIAGRAM IT SHALL CONNECT
 UP STREAM OF THE KITCHEN AND WASHING MACHINE DRAIN. PER
 FBC PL 912.1
  
 2.SHOW LOCATION OF NEW AND EXISTING PIPING ON FLOOR
 PLAN .PER WPB AMEND.TO FBC107.2.1
  
 3. STUDER VENTS SHOULD BE SHOWN ON TOP OF THE VENT
 STACKS. PER WPB AMEND.TO FBC107.2.1
  
 4. SHOW DIMENSIONS FO THE SHOWER AND TOILET SPACE ALONG
 WITH TOTAL DIMENSIONS OF BATHROOM. PER WPB AMEND.TO
 FBC107.2.1
  
 5. ALL PLUMBING DONE WITHOUT A PERMIT SHALL BE EXPOSED
 AND TESTED FOR INSPECTIONS. PER WPB AMEND.TO FBC
 110.3(C)1,2,3