Plan Review Notes
Plan Review Notes For Permit 16071249
Permit Number 16071249
Review Stop E
Sequence Number 1
Notes
Date Text
2016-08-02 13:16:23ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 PROJECT: EXISTING CARPORT
 JOB ADDRESS: 410 31ST ST.
 DESCRIPTION: PERMIT FOR EXISTING ENCLOSED GARAGE
 MAST. PERMIT: 16071249
 REVISION:
  
 1. REGARDLESS OF WHEN THE UNPERMITTED WORK WAS DONE, IT
 IS BEING PERMITTED UNDER THE CURRENT CODE AND THEREFORE
 SHALL COMPLY WITH SUCH ACCORDINGLY.
 2. THE CURRENT APPLICABLE CODES ARE: FLORIDA FIRE
 PREVENTION CODE: 2012, NFPA 1: 2012, NFPA 70, (NEC):
 2011, NFPA 72: 2010, NFPA 101: 2012, FBC- 5TH EDITION:
 2014.
 3. SECTION 107.2.1 OF THE WPB CITY AMENDMENTS REQUIRE
 THAT THE CONSTRUCTION DOCUMENTS BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE PROPOSED WORK AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO CODE REQUIREMENTS. (CLEARLY DEFINE YOUR
 SCOPE OF WORK ON THE PLANS). SUCH DRAWINGS SHALL
 INDICATE THE APPLICABLE DESIGN CODE, AND FURTHERMORE,
 THE DRAWINGS SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. (YOUR NAME AND
 SIGNATURE SHALL APPEAR ON ALL DOCUMENTS).
 4. BY ENCLOSING THE CARPORT YOU ARE CONVERTING IT TO
 HABITABLE SPACE AND THEREFORE SPECIFIC CODE
 REQUIREMENTS APPLY. IN THE ELECTRICAL ASPECT YOU SHALL
 ADDRESS THE REQUIREMENTS OF THE 2011 EDITION OF THE
 NEC. JUST TO NAME A FEW, SEE BELOW:
 A) NEC 210.52 HAS SPACING REQUIREMENTS WHICH DO NOT
 APPEAR TO COMPLY ON THE SUBMITTED DRAWING.
 B) NEC 210.70 HAS LIGHTING REQUIREMENTS THAT ARE NOT
 SHOWN ON THE PLANS.
 C) NEC 210.8 HAS THE GFCI REQUIREMENTS
 D) NEC210.12 HAS THE ARC-FAULT REQUIREMENTS
 E) NEC 406.12 HAS THE REQUIREMENTS FOR THE
 TAMPER-RESISTANT RECEPTACLES.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  