| 2016-08-02 13:16:23 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | PROJECT: EXISTING CARPORT |
| | JOB ADDRESS: 410 31ST ST. |
| | DESCRIPTION: PERMIT FOR EXISTING ENCLOSED GARAGE |
| | MAST. PERMIT: 16071249 |
| | REVISION: |
| | |
| | 1. REGARDLESS OF WHEN THE UNPERMITTED WORK WAS DONE, IT |
| | IS BEING PERMITTED UNDER THE CURRENT CODE AND THEREFORE |
| | SHALL COMPLY WITH SUCH ACCORDINGLY. |
| | 2. THE CURRENT APPLICABLE CODES ARE: FLORIDA FIRE |
| | PREVENTION CODE: 2012, NFPA 1: 2012, NFPA 70, (NEC): |
| | 2011, NFPA 72: 2010, NFPA 101: 2012, FBC- 5TH EDITION: |
| | 2014. |
| | 3. SECTION 107.2.1 OF THE WPB CITY AMENDMENTS REQUIRE |
| | THAT THE CONSTRUCTION DOCUMENTS BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE PROPOSED WORK AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO CODE REQUIREMENTS. (CLEARLY DEFINE YOUR |
| | SCOPE OF WORK ON THE PLANS). SUCH DRAWINGS SHALL |
| | INDICATE THE APPLICABLE DESIGN CODE, AND FURTHERMORE, |
| | THE DRAWINGS SHALL BEAR THE NAME AND SIGNATURE OF THE |
| | PERSON RESPONSIBLE FOR THE DESIGN. (YOUR NAME AND |
| | SIGNATURE SHALL APPEAR ON ALL DOCUMENTS). |
| | 4. BY ENCLOSING THE CARPORT YOU ARE CONVERTING IT TO |
| | HABITABLE SPACE AND THEREFORE SPECIFIC CODE |
| | REQUIREMENTS APPLY. IN THE ELECTRICAL ASPECT YOU SHALL |
| | ADDRESS THE REQUIREMENTS OF THE 2011 EDITION OF THE |
| | NEC. JUST TO NAME A FEW, SEE BELOW: |
| | A) NEC 210.52 HAS SPACING REQUIREMENTS WHICH DO NOT |
| | APPEAR TO COMPLY ON THE SUBMITTED DRAWING. |
| | B) NEC 210.70 HAS LIGHTING REQUIREMENTS THAT ARE NOT |
| | SHOWN ON THE PLANS. |
| | C) NEC 210.8 HAS THE GFCI REQUIREMENTS |
| | D) NEC210.12 HAS THE ARC-FAULT REQUIREMENTS |
| | E) NEC 406.12 HAS THE REQUIREMENTS FOR THE |
| | TAMPER-RESISTANT RECEPTACLES. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |