| 2016-08-03 17:27:49 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | PROJECT NAME: |
| | JOB ADDRESS: 1230 WELLINGTON ST. |
| | DESCRIPTION: REMODEL-FILL IN OF CARPORT |
| | MASTER PERMIT:16071244 |
| | |
| | 1. WHAT IS BEING DONE TO REPLACE THE LOST ILLUMINATION |
| | IN THE EXISTING LIVING ROOM AFTER REMOVING THE CEILING |
| | FIXTURE? |
| | 2. FBC-ER3903.3/NEC 210.70(A)(2)(C): THERE HAS TO BE |
| | LIGHTING FOR THE EXISTING STAIRS. IF THERE IS AN |
| | ELEVATION CHANGE OF SIX STEPS OR GREATER AT THE |
| | EXISTING STAIRS, A SWITCH IS REQUIRED AT THE TOP AND |
| | BOTTOM OF STAIRS. |
| | 3. FBC-RE3901/NEC 210.52(A): THERE ARE MANY WALLS |
| | REQUIRING OUTLETS THROUGHOUT THE NEWLY CONSTRUCTED AREA |
| | NOT MEETING THE MINIMUM REQUIREMENTS OF THE CODE. |
| | 4. FBC-ER3901/NEC 210.52(C): HAS SPACING REQUIREMENTS |
| | FOR THE OUTLETS ON THE KITCHEN COUNTERS WHICH ARE NOT |
| | REFLECTED ON THE SUBMITTED DRAWING. |
| | 5. FBC-RE3905.6.2/NEC 314.27(A) LUMINAIRE OUTLETS. |
| | BOXES USED AT LUMINAIRE OR LAMPHOLDER OUTLETS IN A |
| | CEILING SHALL BE REQUIRED TO SUPPORT A LUMINAIRE |
| | WEIGHING A MINIMUM OF 50 LB. ADD THIS TO THE NOTES ON |
| | CEILING BOXES ON PAGE. |
| | 6. FBC-RE3902.12/NEC 210.12B - OUTLETS IN THE NEW |
| | CONSTRUCTION SHALL BE AFCI PROTECTED. |
| | 7. FBC-R4002.14 NEC 406.12 TAMPER-RESISTANT RECEPTACLES |
| | IN DWELLING UNITS. IN ALL AREAS SPECIFIED IN 210.52, |
| | ALL 125-VOLT, 15 AND 20 AMPERE RECEPTACLES SHALL BE |
| | LISTED TAMPER RESISTANT RECEPTACLES. |
| | 8. NEC 215.5: A RISER DIAGRAM SHOWING FEEDER DETAILS |
| | ALONG WITH RESPECTIVE LOAD CALCS SHALL BE PROVIDED. |
| | THIS DIAGRAM SHALL INCLUDE CONDUCTOR SIZING AND |
| | INSULATION TYPE. FURTHERMORE, IT SHALL BE SITE |
| | SPECIFIC. THE RISER DIAGRAM AS SUBMITTED DOES NOT |
| | COMPLY AND THE LOAD CALCS DO NOT MATCH THE SUBMITTED |
| | PANEL SCHEDULE. |
| | 9. REVISE THE SUBMITTED PANEL SCHEDULE KVA & VOLTAGE |
| | COLUMNS. |
| | 10. THE NOTES ON THE PLAN REFER TO THE 150 AMP SERVICE |
| | AS REQUIRED/PROVIDED. YOU SHALL INDICATE IF THE |
| | EXISTING SERVICE IS A 150 AMP AND WILL REMAIN AS IS OR |
| | IF ANY CHANGE BESIDES THE ADDITION OF THE REQUIRED |
| | CIRCUITS IS TO BE PERFORMED. |
| | 11. FBC-R314: YOU SHALL INSTALL SMOKE DETECTOR AS PER |
| | CODE FOR NEW CONSTRUCTION. IF YOU HAVE GAS/FOSSIL FUEL |
| | BURNING APPLIANCES OR AN ATTACHED GARAGE YOU SHALL ALSO |
| | COMPLY WITH THE CARBON MONOXIDE REQUIREMENTS. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |