| 2016-08-01 14:35:01 | REVIEW 2014 5TH FBC ED. NEC 2011 |
| | MARIO VALDES |
| | ELECTRICAL PLAN EXAMINER |
| | 561-805-6713 |
| | [email protected] |
| | |
| | 1) FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| | UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS |
| | SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING |
| | OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| | BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND |
| | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, |
| | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE |
| | OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS |
| | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO |
| | SECTION 107.3.5). |
| | |
| | 2) FBC-107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING |
| | PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON |
| | SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. |
| | THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, |
| | SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO |
| | RECORDS MANAGEMENT |
| | |
| | 3) NEC 215.5 PROVIDE A DIAGRAM SHOWING FEEDER ROUTING, |
| | SERVICE RISER DIAGRAM TO SHOW POWER SOURCE FROM UTILITY |
| | SERVICE. |
| | |
| | 4) FBC-E C405.7.3 VOLTAGE DROP. FEEDERS & CUSTOMER |
| | OWNED SERVICE CONDUCTORS SHALL BE SIZED FOR A MAXIMUM |
| | OF 2% VOLTAGE DROP. BRANCH CIRCUITS SHALL BE SIZED FOR |
| | A MAXIMUM OF 3% VOLTAGE DROP. |
| | |
| | 5) PROVIDE AIC RATING OF OCPD AND ELECTRICAL EQUIPMENT |
| | NEC 110.9 & 110.10, FPL LETTER MIGHT BE REQUIRED TO |
| | VERIFY AVAILABLE FAULT CURRENT NEC 110.24(A) |
| | |
| | 6) OUTDOOR ELECTRICAL EQUIPMENT SHALL BE INSTALLED IN |
| | SUITABLE ENCLOSURES AND SHALL BE PROTECTED FROM |
| | ACCIDENTAL CONTACT BY UNAUTHORIZED PERSONNEL, OR BY |
| | VEHICULAR TRAFFIC, OR BY ACCIDENTAL SPILLAGE OR LEAKAGE |
| | FROM PIPING SYSTEMS. IF APPLICABLE PLEASE PROVIDE |
| | PROPER GUARDING NEC 110.27 |
| | |
| | ADDITIONAL COMMENTS MAY BE ADDED ON THE NEXT SUBMITTAL |
| | IF NECCESSARY. |
| | |