| 2016-07-29 06:39:09 | |
| | 1.) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| | LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL |
| | GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC. |
| | G2413. |
| | |
| | 2.)THE GAS DRAWING SHOWS THE GAS PIPING ENTERING THE |
| | STRUCTURE. SUBMIT A GAS RISER SHOWING ALL GAS |
| | APPLIANCES ON THE SYSTEM, THE BTU LOAD OF EACH |
| | APPLIANCE AND THE LONGEST LENGTH OF PIPING FROM THE |
| | POINT OF DELIVERY TO THE MOST REMOTE OUTLET AND THE |
| | LOAD OF EACH SECTION. |
| | |
| | 3) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, ( |
| | METER OR MP REGULATOR) TO THE MOST REMOTE OUTLET IN THE |
| | BUILDING AND / OR SYSTEM PER THE 2014 FBC-FUEL GAS |
| | SEC.402.4.1 OR 2014 FBC-RES. SEC. G 2413.3. |
| | |
| | 4) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| | ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES. |
| | SEC. G2413.2. . |
| | |
| | 5) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / |
| | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| | FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014 |
| | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED |
| | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| | INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. |
| | |
| | 6) INDICATE ON THE PLANS AND PERMIT APPLICATION IF THIS |
| | IS A NEW INSTALLATION OR IF IT IS REPLACING AN EXISTING |
| | TANKLESS WATER HEATER IN THE SAME LOCATION. |
| | |
| | 7) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE |
| | LOCATION OF THE TANKLESS WATER HEATER IN RELATION TO |
| | ANY OPERABLE DOORS OR WINDOOWS. THE LOCATION OF THE |
| | WATER HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS. |
| | |
| | |
| | |