Plan Review Notes
Plan Review Notes For Permit 16071135
Permit Number 16071135
Review Stop B
Sequence Number 2
Notes
Date Text
2016-09-20 13:25:37BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16071135
 ADD: 1897 PALM BEACH LAKES BLVD UNITS 118,119,120,
 121,122 & 123.
 CONT: HALLMARK & SONS INC.
 TEL: 561-644-3498
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. SEPT. 20/ 2016
 ACTION: DENIED
  
 1) 2ND REQUEST. SHEET A1 & A2 SHOW THE RECONFIGURATION
 OF COMMERCIAL CONDOMINIUM UNITS. UNITY OF TITLE.
 THE PROPOSED BUILDING STRUCTURE TRANSGRESSES LEGAL
 BOUNDARY LINES BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'. A 'UNITY OF TITLE' SHALL BE RECORDED AT THE
 COUNTY COURTHOUSE. SUBMIT A COPY OF THE RECORDED 'UNITY
 OF TITLE' DOCUMENT SO THAT FBC TABLE 601 BOUNDARY LINE
 REQUIREMENTS MAY BE DEEMED NOT APPLICABLE.
 SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
 *********************************************
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 2-6) COMPLIED
  
 7) 2ND REQUEST. PLEASE IDENTIFY THE NEW SUITES SO
 TRACKING OF THE UNITS WILL SHOW THE HISTORY. SHEET A2
 SHOWS TWO NEWLY DEFINED TENANT SPACES BUT THERE HAS
 BEEN NO IDENTIFICATION AS THE NEW TENANT ADDRESS FOR
 EACH SPACE. 107.2.1. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED, PROVIDE THE TENANT ADDRESS
 FOR EACH SPACE.
  
 8-9) COMPLIED.
  
 10) 2ND REQUEST. SEMI-COMPLIED. SHEET A7 SHOWS WIND
 DESIGN CRITERIA, BUT IT IS ILLEGIBLE, TO SMALL AND
 FUZZY TO READ. I ALSO BELIEVE THE EXPOSURE PROVIDED IS
 A B EXPOSURE. PLEASE REVIEW TO THE NORTHEAST THE
 CONVERGENCE OF PALM BEACH LAKES & I-95 CREATES A C
 EXPOSURE AS WELL AS TO THE NORTHWEST A LAKE AND AGAIN
 I-95. FBC-B 1609.4.2 SURFACE ROUGHNESS CATEGORIES.
 SURFACE ROUGHNESS C. OPEN TERRAIN WITH SCATTERED
 OBSTRUCTIONS HAVING HEIGHTS GENERALLY LESS THAN 30.
 THIS CATEGORY INCLUDES FLAT OPEN COUNTRY, AND
 GRASSLANDS. THIS SURFACE ROUGHNESS SHALL ALSO APPLY TO
 ANY BUILDING LOCATED WITHIN SURFACE ROUGHNESS B TYPE
 TERRAIN WHERE THE BUILDING IS WITHIN 100 FEET
 HORIZONTALLY IN ANY DIRECTION OF OPEN AREAS OF SURFACE
 ROUGHNESS C OR D-TYPE TERRAIN THAT EXTENDS MORE THAN
 600 FEET IN THE UPWIND DIRECTION AND A WIDTH GREATER
 THAN 150 FEET.
 1ST ROUND COMMENT. THE NEW TENANT SPACE TO THE RIGHT
 SHOWS NEW DOUBLE EGRESS DOOR ON THE FRONT OF THE
 BUILDING. PLEASE PROVIDE THE WIND DESIGN CRITERIA FOR
 THIS OPENING.
 2014 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING
 INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN,
 REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF
 THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE:
  
 10.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND
 GUST), MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND
 SPEED, VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 10.2. RISK CATEGORY.
  
 10.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
  
 10.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 10.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 11) SEMI-COMPLIED. PLEASE NOTE ONLY (1) SET OF PRODUCT
 APPROVALS WERE SUBMITTED, (2) REQUIRED FOR EACH SET OF
 PLANS. 107.1. SUBMITTAL DOCUMENTS.
  
 12-13) NOT REQUIRED, NO SHUTTERS REQUIRED.
  
 14)SEMI-COMPLIED. PLEASE NOTE ONLY (1) SET OF PRODUCT
 APPROVALS WERE SUBMITTED, (2) REQUIRED FOR EACH SET OF
 PLANS. 107.1. SUBMITTAL DOCUMENTS. ADMINISTRATION
 107.3.4 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL BE RESPONSIBLE FOR REVIEWING AND COORDINATING
 SUBMITTAL DOCUMENTS PREPARED BY OTHERS, INCLUDING
 PHASED AND DEFERRED SUBMITTAL ITEMS, FOR COMPATIBILITY
 WITH THE DESIGN OF THE BUILDING. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE
 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 15-18) COMPLIED.
  
 19) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  