| Plan Review Notes For Permit 16071135 |
| Permit Number |
16071135 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-08-24 05:33:04 | 1) SHT. A4 - THE LENGTH OF THE TOILET COMPARTMENTS | | | SHALL COMPLY WIYH 2014 FPC SEC. 405.3.1. | | | 2) SHT. A4 - TOILET COMPARTMENTS IN GANG RESTROOMS - | | | DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACE FOR | | | ANY FIXTURE PER THE 2014 FAC SEC.603.2.3. | | | 3) SHT. A4 - THE GRAB BARS SHALL BE MEASURED FROM THE | | | FINISH FLOOR TO THE TOP OF THE GRIPPING SURFACE PER | | | 2014 FAC SEC. 609.4. | | | 4) SHT. A4 - THE GRAB BAR BEHIND THE WATER CLOSET SHALL | | | COMPLY WITH FIGURE 604.5.2 OF THE 2014 FAC & SEC. | | | 604.5.2. | | | 5) THE TOILET PAPER DISPENSER SHALL BE LOCATED 7-9 | | | INCHES FROM THE FRONT OF THE WATER CLOSET TO THE | | | CENTERLINE OF THE DISPENSER. 22014 FAC SEC. 604.7. | | | 6) SHT. A4 - PLEASE NUMBER THE DETAILS. FBC 107.2.1. | | | 7) SHT. P3.1 NOTE #4 REFERS TO SHT. P5.1 FOR DETAILS OF | | | HW, CW & HWR BUT P5.1 SHOWS PIPE SUPPORT. CLARIFY. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|