Plan Review Notes
Plan Review Notes For Permit 16071135
Permit Number 16071135
Review Stop M
Sequence Number 1
Notes
Date Text
2016-08-03 10:16:241ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16071135
 8/3/16
  
 1) THE TOILET ROOM EXHAUST FAN CAPACITIES SHALL BE
 SIZED AT 70 CFMS PER WATER CLOSET OR URINAL IF TO BE
 OPERATED INTERMITTENTLY.
  
 2) ENERGYGAUGE/ASHRAE 90.1 COMPLIANCE SUBMITTAL: PLEASE
 COMPLETE THE CHECKLIST ON PAGE 1 AND SUBMIT THE
 MANDATORY COMPLIANCE CHECKLIST ALL APPLICABLE BOXES
 CHECKED OFF.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  