| Notes |
| Date |
Text |
| 2016-08-03 10:16:24 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #16071135 | | | 8/3/16 | | | | | | 1) THE TOILET ROOM EXHAUST FAN CAPACITIES SHALL BE | | | SIZED AT 70 CFMS PER WATER CLOSET OR URINAL IF TO BE | | | OPERATED INTERMITTENTLY. | | | | | | 2) ENERGYGAUGE/ASHRAE 90.1 COMPLIANCE SUBMITTAL: PLEASE | | | COMPLETE THE CHECKLIST ON PAGE 1 AND SUBMIT THE | | | MANDATORY COMPLIANCE CHECKLIST ALL APPLICABLE BOXES | | | CHECKED OFF. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|